L100-M Inverter
17
B_32: Reactive current setting
– The inverter’s D_02 monitor function displays the
motor current. The display accuracy is normally ±20%, provided that the following
conditions exist:
• A single motor with standard frame size and characteristics is connected
• The inverter’s output frequency is at 50% or higher of the maximum output frequency
• The inverter’s output current is within the rated current
However, it will be necessary to calibrate the display accuracy via B_32 adjustment of
the internal no-load reactive motor current if any of these conditions exist:
• The motor is smaller than the standard maximum recommended for the inverter
• The motor is a two-pole motor type
• Two or more motors are connected in parallel to the inverter (be sure to multiply the
current by the number of motors when setting B_32)
For general purpose motors that have an undetermined internal no-load (reactive) motor
current, use the following table for typical current values. For special motors, consult the
manufacturer of your particular motor.
“B” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–MFU2
–MFR2
Units
B_32 Reactive current setting
Calibrate detection of motor’s
no load (reactive current) to
improve D_02 display
accuracy, range is 0 to 32
Amperes
✔
40% rated current
A
IO 0.00A
Motor
200V Class
HP
kW
Poles
at 50 Hz
at 60 Hz
1/8
0.1
4
0.6 A
0.5 A
1/4
0.2
2
0.6 A
0.4 A
4
0.8 A
0.7 A
—
0.3
4
1.1 A
1.1 A
1/2
0.4
2
1.2 A
0.9 A
4
1.7 A
1.2 A
6
1.9 A
1.5 A
1
0.75
2
1.9 A
1.3 A
4
2.2 A
1.7 A
6
1.8 A
2.2 A