7-19
Contents and display
Extension
function
code
➤
➤
➤
➤
1
2
➤
1
2
FUNC
FUNC
➤
Electronic
thermal
level
adjustment
➤
➤
➤
➤
➤
➤
➤
➤
Set the electronic thermal level. Set the thermal level in accordance with the rated current of the
motor in units of 1 (%).
Adjustment level =
Motor rated current
Inverter rated current
100
Initial value
0
Inverter current (A)
Inverter rated current
Setting method
20
100
150
200
20%
120%
➤
➤
➤
➤
1
2
➤
1
2
FUNC
FUNC
➤
Electronic
thermal
character-
istic
selection
Select the electronic thermal characteristics. Set the thermal characteristics in accordance with
the load to be used. For free setting of set value 2, the current and frequency can be set by each
remote operator.
Initial value
Setting method
Initial value
Set value
Function
0
Constant torque characteristic
1
Reduced torque characteristic
2
Free setting
(Can be set by the remote operator)
100
80
60
0
5
20
60
120
Output current (%)
Output frequency (Hz)
Reduced torque
characteristic
Constant torque
characteristic
(Each characteristic
at 60 Hz or more is 100%.)
Motor
poles
setting
for motor
speed
monitor
Time(s)
➤
➤
➤
➤
1
2
➤
1
2
FUNC
FUNC
➤
Set the pole number of motor to convert output frequency into motor rotation speed on monitor
mode funciton
2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 24, 32, 36, 48
Initial value
Setting method
.
Settable numbers