12-10
Display
(Function mode 1)
(Function mode 2)
Setting, change
sequence
Function
Function
Initialization display
Initialization
contents
Setting contents
No.
name
contents
19
F-26
Frequency
LIMIT L
0000.0 Hz
0 Hz
0 to 120.0
The lower limit of the frequency
Frequency lower limiter
(400) Hz
to be set is set. When the lower
limiter
setting
limit is 0, the setting is invalid.
Frequency
LIMIT H
0000.0 Hz
0 Hz
0 to 120.0
The upper limit of the frequency
upper
(400) Hz
to be set is set. When the upper
limiter
limit is 0, the setting is invalid.
setting
20
F-27
Jump
JUMP F1
0000.0 Hz
0 Hz
0 to 400 Hz
• The section where frequencies
Jump
frequency
are to be jumped is set.
frequency setting (1)
• Up to three locations can be
set.
• When the number of locations
is 0, the setting is invalid.
Jump
JUMP F2
0000.0 Hz
0 Hz
0 to 400 Hz
frequency
setting (2)
Jump
JUMP F3
0000.0 Hz
0 Hz
0 to 400 Hz
frequency
setting (3)
Jump
JUMP W
0.5 Hz
0.5 Hz
0 to 9.9 Hz
• The frequency width where
frequency
frequencies are jumped is set.
width setting
21
F-28
STOP key
STOP-SW
ON
ON
ON: STOP key
Whether or not to make the
validity
valid
STOP key valid during terminal
selection
OFF: STOP key
running is selected. In the
during
invalid
Remote mode, the STOP key is
terminal
always valid.
running
22
F-29
Running
F/R SW
FRE
FRE
FWD/REV/
FWD: Only forward run
direction
FRE
REV: Only reverse run
selection
FRE: Both forward run and
reverse run valid
Reverse run
F/R PREV
OFF
OFF
ON/OFF
Reverse run prevention
prevention
ON:
selection
OFF:
Reduced
F/R RVS
6
6
0 to 6
voltage
soft start
setting
23
F-30
Maximum
F-MAX-L
120 Hz
120 Hz
120/400 Hz
Maximum frequency switching:
frequency
120: 120 Hz 400: 400 Hz
selection
24
F-31
Analog input IN ANA
10 V
10 V
10/5
Input voltage maximum level
External
voltage
10: Max. 10 V 5: Max. 5 V
analog
selection
frequency External
IN EXS
0000.0 Hz
0 Hz
0 to 120.0 (400)
• Frequency at which the
command
frequency
external input starts
start setting
External
IN EXE
0000.0 Hz
0 Hz
0 to 120.0 (400)
• Frequency at which the
frequency
external input is maximized
end setting
External
IN EX%S
000%
0%
0 to 100
• Input start level
frequency
start setting
rate
External fre- IN EX%E
100%
100%
0 to 100
• Input maximum level
quency end
setting rate
External
IN LEVEL
0 Hz
0 Hz
0 Hz/ExS
EXS: Start at EX%S setting
command
rate or less
start point
selection