12-5
12.3
Function mode
Function mode list when the remote operator is used
• Function mode initial values and display contents
Initial display contents, initialization, and change ranges are displayed in the table
indicated below.
Display
(Function mode 1)
(Function mode 2)
Setting, change
sequence
Function
Function
Initialization display
Initialization
contents
Setting contents
No.
name
contents
1
F-00
Base
F-BASE
0060 Hz
60 Hz
30 to 120 (400)
• When 120 Hz is switched to
frequency
400 Hz by F-30, a frequency
setting
more than 120 Hz can be set.
2
F-01
Maximum
F-MAX
0060 Hz
60 Hz
30 to 120 (400)
frequency
setting
3
F-02
Start
Fmin
0.50 Hz
0.5 Hz
0.1 to 9.9
• The equipment starts running
frequency
at this set value.
adjustment
4
F-03
Motor input
AVR AC
460 V
230/460
200,215,220,230
• The motor input voltage is set.
Input
voltage
/380,400,415
voltage
setting
440,460,480
AVR
AVRDEC
OFF
OFF
ON/OFF
• ON or OFF of the AVR
function
function for deceleration
for
is set. When dynamic
decelera-
braking torque is necessary
tion
for deceleration, OFF is set.
5
F-04
Control
CONTROL
VC
VC
VC, VP1, VP2,
• VC, VP1, VP2, VP3:
method
VP3, SLV, V2
V/F characteristics
setting
SLV:Sensorless vector control
V2:Sensor vector control
6
F-05
Autotuning
AUX AUTO
NOR
NOR
NOR/AUT/NRT
• At the first running after
Motor
setting
AUT/NRT is set, the
constant
autotuning measurement
(NOTE 1)
operation is executed.
Motor data
AUX DATA
NOR
NOR NOR: Old Hitachi
• The autotuning motor data
selection
general purpose
before starting autotuning
TMO: New
measurement is data
Hitachi general
equivalent to NOR.
purpose
AUT: Auto-
tuning data
Motor
AUX K
005.50 kW
Rated capacity
3.7 to 160
• Set a capacity smaller than the
capacity
of each inverter
rated capacity as capacity
setting
data.
Motor pole
AUX P
4p
4p
2, 4, 6, 8
• The number of poles of the
count
motor to be used is set.
setting
Motor
AUX R1
1.004
Rated capacity
0 to 65.535
constant
of each inverter
R1 setting
Motor
AUX R2
0.776
Rated capacity
0 to 65.535
constant
of each inverter
R2 setting
Motor
AUX L
13.16 mH
Rated capacity
0 to 655.35
constant
of each inverter
L setting
NOTE 1: The motor constants R1, R2, L, M, J, Kp, Ti, and KPP vary with the capacity.