3 INSTALLATION AND MODULE MOUNTING
3-13
3.8 Mounting
Design
3.8.1 Mounting
limitations
When mounting I/O modules on the mount base, make sure that the total of the current
consumptions of all of those I/O modules is within the specified output current of the power
supply module. The tables below show the rated output currents of available power supply
modules and consumption currents of available I/O modules.
Item Specification
Model LWV450,
LWV550
LWV460
Output
current
12 VDC
3.5 A
3.5 A
5 VDC
0.8 A
2.0 A
Model
12 VDC
5 VDC
LWS410
10 mA
150 mA
LWI400
0
5 mA + 2 mA × n
LWI450, LWI460, LWI470
0
4 mA + 2 mA × n
LWI600
0
5 mA + 2 mA × n
LWI650
0
4 mA + 2 mA × n
LWO400
22 mA × n
25 mA
LWO450, LWO460
22 mA × n
15 mA
LWO600
16 mA × n
25 mA
LWO610
16 mA × n
25 mA
LWO650
16 mA × n
15 mA
LWO670
8 mA + 20 mA × n
8 mA
LWA400 to LWA404, LWA421 to LWA423
150 mA
40 mA
LWA430, LWA435
350 mA
50 mA
LWA500, LWA501
250 mA
45 mA
LWA450, LWA460
260 mA
40 mA
LWA550, LWA551
300 mA
40 mA
LWA560
250 mA
40 mA
LWC400, LWC401, LWC402
40 mA
8 mA
n: Is the number of data points that are turned on simultaneously in the I/O module.
Содержание HSC-2100
Страница 1: ......
Страница 2: ......
Страница 24: ...1 GENERAL INFORMATION ...
Страница 38: ...2 SPECIFICATIONS OF INDIVIDUAL MODULES ...
Страница 78: ...3 INSTALLATION AND MODULE MOUNTING ...
Страница 92: ...4 WIRING ...
Страница 101: ...This Page Intentionally Left Blank ...
Страница 102: ...5 MAKING USE OF MODULES ...
Страница 150: ...6 MAINTENANCE ...
Страница 163: ...This Page Intentionally Left Blank ...
Страница 164: ...7 APPENDIX ...
Страница 169: ...This Page Intentionally Left Blank ...