5 MAKING USE OF MODULES
5-7
5.2.3 Data
area
formats
(1) Formats for analog input modules
(a) Format used in remote I/O transfer -- for LWA400 to 404, LWA421 to 423, LWA430,
LWA450, LWA460, LWC400 to 402
Data area: Registered data area (or EW area)
2
15
2
11
2
10
2
0
1st word
S
···
S
Channel 0 input data
2nd word
S
···
S
Channel 1 input data
3rd word
S
···
S
Channel 2 input data
4th word
S
···
S
Channel 3 input data
• If an input value overflows in the data area, the result will be as follows:
For positive-value overflow: 2,047
For negative-value overflow: -2,048
• If an input value is insignificant, it is automatically set to H8000.
(b) Format used in remote I/O transfer -- for LWA435
Data area: Registered data area (or EW area)
2
15
2
13
2
12
2
0
1st word
S
···
S
Channel 0 input data
2nd word
S
···
S
Channel 1 input data
3rd word
S
···
S
Channel 2 input data
4th word
S
···
S
Channel 3 input data
• If an input value overflows in the data area, the result will be as follows:
For positive-value overflow: 8,191
For negative-value overflow: -8,191
• If an input value is insignificant, it is automatically set to H8000.
Data: Values in the range -2,048 to 2,047
Sign
Data: Values in the range -8,191 to 8,191
(the value -8,192 is not displayed)
Sign
Содержание HSC-2100
Страница 1: ......
Страница 2: ......
Страница 24: ...1 GENERAL INFORMATION ...
Страница 38: ...2 SPECIFICATIONS OF INDIVIDUAL MODULES ...
Страница 78: ...3 INSTALLATION AND MODULE MOUNTING ...
Страница 92: ...4 WIRING ...
Страница 101: ...This Page Intentionally Left Blank ...
Страница 102: ...5 MAKING USE OF MODULES ...
Страница 150: ...6 MAINTENANCE ...
Страница 163: ...This Page Intentionally Left Blank ...
Страница 164: ...7 APPENDIX ...
Страница 169: ...This Page Intentionally Left Blank ...