5 MAKING USE OF MODULES
5-30
③
As an example, we will register the analog module mounted in slot 0 in the I/O unit, which
is shown in Figure 5-6, “An Example Hardware Configuration in Which Four Modules Are
Mounted: Three Analog and One Counter.” To accomplish this, choose the model number
“LWA400” in the “Module name(M)” list box, as shown below.
If you are a user of the S10V Ladder Chart System, Ver. 01 and Rev. 21 or later, specify the
model number of the analog module directly.
If not (i.e., you are a user of the S10V Ladder Chart System, Ver. 01 and Rev. 20 or earlier,
or the ladder chart system for S10/2
α
and S10mini controllers), you cannot specify the
model number directly. It must be replaced with its registration model number according
to the information given in the table below, and the registration model number must be
specified instead.
• The registration model numbers for analog I/O modules in the case of S10V Ladder Chart
System, Ver. 01, Rev. 20 or earlier, or S10/2
α
/ S10mini Ladder Chart System:
Actual model number
Registration model number
LWA400 PAF300
LWA401 PAF309
LWA402 PAF320
LWA403 PAF329
LWA404 PAF309
LWA421 PAF301
LWA422 PAF301
LWA423 PAF301
LWA430 PAF300
LWA450 PAN300B
LWA460 PAN301B
LWC400 PTF320
LWC401 PTF300
LWC402 PTF300
Choose the model number
“LWA400” in the list box.
Содержание HSC-2100
Страница 1: ......
Страница 2: ......
Страница 24: ...1 GENERAL INFORMATION ...
Страница 38: ...2 SPECIFICATIONS OF INDIVIDUAL MODULES ...
Страница 78: ...3 INSTALLATION AND MODULE MOUNTING ...
Страница 92: ...4 WIRING ...
Страница 101: ...This Page Intentionally Left Blank ...
Страница 102: ...5 MAKING USE OF MODULES ...
Страница 150: ...6 MAINTENANCE ...
Страница 163: ...This Page Intentionally Left Blank ...
Страница 164: ...7 APPENDIX ...
Страница 169: ...This Page Intentionally Left Blank ...