The server’s cooling airflow enables the system to operate in an ambient temperature
range of 10°C to 35°C when mounted in a rack or cabinet with associated components
required to make up a storage system. The storage system administrator is responsible
for ensuring that the ambient temperature within the rack does not exceed the 35°C
operating limit.
The server continues to operate following the failure of a single fan and during the
temporary removal of a fan for replacement. Replace a failed fan as soon as possible.
Caution: If a fan has failed, replace the fan as soon as possible to reduce the
amount of time the server is operating with reduced airflow.
The fans are contained within two assemblies, each containing a single variable-speed
fan. Fan assemblies are located behind the front bezel. Each fan assembly is secured to
the chassis with two thumbscrews and a blind-mate electrical connector; no tools are
required to remove or install a fan assembly.
Two fan status LEDs provide fan status information. These LEDs are located behind the
bezel on the right side of the chassis.
Item
Description
1
Fan 1 (left)
2
Fan 2 (right)
3
Fan 1 status LED
4
Fan 2 status LED
Fans
Chapter 4: Hitachi NAS Platform server components
Hitachi NAS Platform Series 5000 Hardware Reference
29