7. INSTRUCTIONS FOR INSTALLATION [Instructions on Electrical Wiring]
7.6 Instructions on Electrical Wiring
7.6.1 Power Source Transformer and Power Cable
Prepare a power source transformer with adequate
capacity. Also, use a power cable with adequate
length and size. Otherwise, a voltage drop will oc-
cur when attempting to start the
A
, and as
a result the motor will fail to start. A voltage drop
will also occur during operation, which deenergizes
the control circuit and shut the air compressor down.
To control a drop of starting voltage within an al-
lowable range (5% of the rated voltage), use the
adequate power source transformer and power
cable as follows:
200V Spec.
400V Spec.
200V Spec.
400V Spec.
Power Transformer
Capacity (kVA)
Power Cable
Thickness (mm
2
)
50
75
Over 38, Max.50
Over 60, Max.100
Over 14, Max.50
Over 38, Max.100
Type
22kW
37kW
These are values for the cables less than 10m in length.
For over 10m, thicker cable is required. In such case,
keep the thickness below its maximum value on the
compressor side by using intermediate terminals.
1. Personnel who carry out the wiring work must have a license. Ask personnel who have license. Wir-
ing work by personnel without license may cause troubles like electric shock accident.
2. Do not take the protective relay off the compressor or make any modification which might hinder its
relay function on the electrical circuit. Such modification will remove its protective functions and may
cause to serious accident like burning the compressor. Ask your dealer if you must have a modifica-
tion to the unit.
3. Be sure to turn the POWER OFF to get rid of electric shock accident, when the cover of starter should
be removed for wiring work or inspection. Attach a plate on the POWER side saying “Maintenance
Work. Do Not Electrifying” to prevent other workers from re-inputting the POWER.
WARNING
●
Be sure to equip a earth leakage circuit breaker to the Power. Wiring with only disconnector like
Knife Switch is not sufficient and may not protect the compressor and cause burning when short
circuit occurs.
●
Be sure that the compressor is appropriately grounded. If not, this can cause electric shock accident
or shutdown to the compressor. Do not use Steel Skeleton as a ground for the compressor. This may
cause malfunction. Ground the cable by itself into the earth.
CAUTION
Voltage imbalance must be 1% or lower between any two pahses.
200V
Spec.
400V
Spec.
22kW
37kW
EXK225 200A
EX400B 225A
or
or
EX225K 175A
EX225K 225A
EX100B 100A
EXK225 150A
or
or
EX100BK 75A
EX225K 125A
Earth leakage
circuit breaker
Type (Hitachi)
Use an earth leakage circuit breaker with current sensitivity of 200 mA.
Type
IMPORTANT
7.6.2 Connecting earth leakage circuit breaker
Be sure to use a earth leakage circuit breaker for
the Circuit Breaker. For motor protection,
Hitachi’s genuine earth leakage circuit breaker
must be equipped to the main POWER line of the
compressor. If earth leakage circuit breaker
other than Hitachi brand is used, ask your dealer
because its specific condition is different.