Offset
Description
Values
Read/Write
Availability
VRF
RAC
ATW
19
Temperature setting with 0.5°C inter-
vals status
ºC x10 (19.5ºC read as
195)
Read
O
20
Heating temperature setting for AUTO
Cool/Heat status
ºC
Read
O
21
Heating Temperature setting for AUTO
Cool/heat with 0.5°C intervals status
ºC x 10 (19.5ºC read
as 195)
Read
O
22
Cooling Temperature setting for AUTO
Cool/heat status
ºC
Read
O
23
Cooling Temperature setting for AUTO
Cool/heat with 0.5°C intervals status
ºC x 10 (19.5ºC read
as 195)
Read
O
24
Louver status
0 ~ 7 (7 is Auto)
Read
O
25
Air inlet temperature reading
-63ºC ~ 63ºC
Read
O
26
Air outlet temperature reading
-63ºC ~ 63ºC
Read
O
27
Gas pipe temperature reading
-63ºC ~ 63ºC
Read
O
28
Liquid pipe temperature reading
-63ºC ~ 63ºC
Read
O
29
Alarm code
Alarm unit from 7-seg-
ment
Read
O
O(1)
30
Compressor stop cause
(Read unit service ma-
nual)
Read
O
31
Indoor unit expansion valve opening
0~100
Read
O
32
Unit operation condition
0: OFF
Read
O
O
1: Thermo OFF
2: Thermo ON
3: Alarm
33
Remote temperature sensor (THM4)
value
-63ºC ~ 63ºC
Read
O
34
Remote control switch temperature
(only when available in the unit)
-63ºC ~ 63ºC
Read
O
O
35
Remote control switch configuration
b0: 0 Master/1Slave
Read/Write
O
b1: 0 wih RCS/1 Without
RCS
36
Remote control switch group
0: No group
Read/Write
O
1~255
37
CN3 Configuration status
b0: Input 1 open/close
Read
O
b1: Input 2 open/close
b2: Enabled/Disabled
(Indicates if the unit has
CN3 enabled with any
function)
38~49
Reserved
50
Control Unit Run/Stop
0: Stop
Read/Write
O
1: Run
51
Control Unit Mode
0: Cool
Read/Write
O
1: Heat
52
Control Circuit 1 Run/Stop
0: Stop
Read/Write
O
1: Run
53
Control Heat. OTC Zone 1
0: No
Read/Write
O
1: Points
2: Gradient
3: Fix
54
Control Cool. OTC 1
0: No
Read/Write
O
1: Points
2: Fix
OPERATION
PMML0351A rev.4 - 04/2020
12