5.3 UDENDØRSENHEDER
Some state registers about outdoor unit have been added. Using these registers it is now possible to know the status of the refrigerant
cycle. Some control registers have also been added.
Offset
Beskrivelse
Værdier
Læs/Skriv
0
Outdoor Air Temperature
-63ºC ~ 63ºC
Læs
1
Compressor Discharge Temperature
0 ~ 200 ºC
Læs
2
Heating Evaporating Temperature
Læs
3
Number of operating Compressor
Læs
4
Udladningstryk
0.0 ~ 5.0 MPa (0.1 MPa)
Læs
5
Sugetryk
-0.2 ~2.0MPa (0.1 MPa or 0.01MPa depending
unit)
Læs
6
Total Current
0 ~ 255 A
Læs
7
Total Real Frequency
0 ~ 255 Hz
Læs
8
EVO1
0 ~ 100 %
Læs
9
EVO2 / Hot Bypass
0 ~ 100 %
Læs
10
EVB
0 ~ 100 %
Læs
11
Outdoor Unit Option Enabled
0: Disable
Læs/Skriv
1: Enable (it’s possible to use the following
options, also if the value of register 16 “Power
Level Set” is 1)
12
Noise Control Enabled
0: Disable
Læs/Skriv
1: Enable (it’s possible to send the noise level)
13
Noise Control Level Set
0~9 (See the service manual of Outdoor unit,
function db)
Læs/Skriv
14
Power Control Enabled
0: Disable
Læs/Skriv
1: Enable (it’s possible to send the power level)
15
Power Level
0~100%
Læs/Skriv
16
Power Level Set
0~100%
Læs
17
Power Level Current Value
0~100%
Læs
18
Power Control Possible
0: Not possible
Læs
1: Possible
?
N O T E
• Register address is calculated as: 5000+(Modbus_Id*200)+offset
• Modbus_Id as configured by configuration software
DRIFT
PMML0351A rev.4 - 04/2020
150