PMML0175A-rev.1 - 6/2008
HARC-MODBUS - xxxxxxxxxxxxxxxx
15
English
HARC-MODBUS - Installation Manual
6.2 CHILLER: Data available
Address
Name
Description
Values
Read/Write
0
EXIST
Exist
0: Not exist
1: Exist
Read
1
SYSTEM_ADDRESS
Chiller Address
0~ 15 in H-LINK 1
Read
2
(Not used)
(Not used)
(Not used)
(Not used)
3
ONOFF_SET
On/Off setting order:
0: Stop
1: Run
Read/Write
4
MODE_SET
Mode Setting order
0: Cool
1: Heat
Read/Write
5
TEMP_SET_C
COOL setting temperature
(see note *)
Read/Write
6
TEMP_SET_H
HEAT setting temperature
7
CENTRAL_SET
Central Setting
0: Local
1: Remote
Read/Write
8
ONOFF_STATUS
On/Off Status
0: Off
1: On
Read
9
MODE_STATUS
Mode Status
0: Cool
1: Heat
Read
10
TEMP_C_STATUS
COOL Setting Temperature
Status
Read
11
TEMP_H_STATUS
HEAT Setting Temperature
Status
Read
12
WATER_INLET
Inlet temperature
Read
13
WATER_OUTLET
Outlet temperature
Read
14
AMBIENT_TEMPERATURE Ambient temperature
Read
15
OPER_CONDITION
Unit operation condition
0: OFF
1: Thermo OFF
2: Thermo ON
3: Alarm
Read
16
ERROR_CODE_CH
Alarm code for general
CHILLER alarm
Read
17~22
ERROR_CODE_CYC
Alarm code for cycle alarm
(1~6)
Read
23~31
(Not used)
(Not used)
(Not used)
(Not used)
Notes:
– Offset Position is: 40000 + N*32 + Address as shown in table, where N is Water Chiller Address.
– Status (real value) and Set (value ordered) parameters have usually the same value but, in some cases, some of them can be
different. It is recommended to use Set parameters for normal control.
– *) When Temperature Setting and Operation Mode are changed at the same time, order first the operation mode change and
later set the desired temperature.