PMML0175A-rev.1 - 6/2008
HARC-MODBUS - xxxxxxxxxxxxxxxxxx
12
HARC-MODBUS - Installation Manual
6. Operation
6.1 PACKAGED: Data available
Address
(Note 1)
Name
Description
Read/Write
0
EXIST
EXIST:
0:
Not
exist
1:
Exist
Read
1
SYSTEM_ADDRESS
System Address:
0 ~ 15 in H-LINK 1
Read
2
UNIT_ADDRESS
Unit Address:
0 ~ 15 in H-LINK1
Read
3
SET_ONOFF
On/Off setting order:
0: Stop
1:
Run
Read/Write
4
SET_MODE
Mode Setting order:
0:
Cool
1:
Dry
2:
Fan
3:
Heat
4: Auto
Read/Write
5
SET_FAN
Fan Setting order:
0:
Low
1:
Medium
2: High
Read/Write
6
SET_TSET
Setting Temperature: 17ºC ~ 30ºC
Read/Write
7
SET_LOUVER
Louver Setting:
0 ~ 8 (8 is Auto)
Read/Write
8
SET_CENTRAL
Central Setting
Bit 0: On/Off (always can be stopped)
Bit 1: Mode
Bit 2: Setting Temp
Bit 3: Fan
Read/Write
9
READ_ONOFF
On/Off Read:
0: Off
1:
On
Read
10
READ_MODE
Mode Read
0:
Cool
1:
Dry
2:
Fan
3:
Heat
4: Auto
Read
11
READ_FAN
Fan Read
0:
Low
1:
Medium
2: High
Read
12
READ_TSET
Setting Temperature Read
(17ºC to 30ºC)
Read
13
READ_LOUVER
Louver Read
0 ~ 8 (8 is Auto)
Read
14~18
(Not used)
(Not used)
(Not used)
19
ERROR_CODE
Alarm Code
Read
20~21
(Not used)
(Not used)
(Not used)
22
OPER_CONDITION
Unit Operation Condition
0:
OFF
1:
Thermo
OFF
2: Thermo ON
3: Alarm
Read
23~31
(Not used)
(Not used)
(Not used)
Note 1: Offset Position is: 20000 + N*32 + Address as shown in table, where N is Indoor Unit Address.