3.4.8 Capacity Control Flow when
ECOMODE (Energy Saving Mode) is Set
(
ECOMODE
is set to off when shipped from the factory, but may be set according to your needs.)
RUNNING CONTROL
運転管理
ALARM
警 報
1
記 憶
遠 方
REMOTE
表示切替/
ワイドモード
STR
機 能
FUNC
リセット
RESET
SELECT/WIDE
1
表示切替/
ワイドモード
ON
:
Light flashes.
OFF
:
Light goes off.
SELECT/WIDE
表示切替/ワイドモード
Set by button
Execute capacity control in accordance with the following
time charts.
(1) ECOMODE (Energy Saving Mode) setting
When you set to
ECOMODE
by load/unload type con-
trol, if the cycle time for load
→
unload exceeds 30
seconds, the start pressure setting is automatically
lowered until it reaches recovery pr 0.05
MPa to conserve energy.
If 30 seconds is exceeded, the
DISPLAY SWITCH /
WIDE MODE
light flashes; if 30 seconds is not
exceeded, the
DISPLAY SWITCH / WIDE MODE
light lights steadily, and control is executed by pres-
sure setting value of ordinary load/unload type con-
trol.
When using
ECOMODE
(Energy Conservation
Mode), “ECO” is displayed on the monitor screen.
(
page 14)
(2) Precautions when using ECOMODE (Energy
Saving Mode)
Enabling
ECOMODE
(Energy Conservation Mode)
requires an air tank that is one turn larger that the air
tank recommended for load/unload type control.
(
For information concerning the air tank, see
page 41.)
This function is used for load/unload type control, and
operates only for the ordinary pressure setting.
Line pressure
Energy Saving Effect
Load
Unload
Time
Start pressure
(Unload start pressure)
Recovery pressure
(Load recovery pressure)
Start pressure
is automatically
reduced.
: 15 psi
: 7 psi
Factory set upper/lower limit pressure differential
ECOMODE differential pressure
Start pressure is automatically reduced to 1 cycle per 30 seconds.
※
Start pressure = Cutout pressure
※
Recovery pressure = Cutin pressure
According to alteration of the pressure setting value of
section 3.4.1, by setting
start pressure 2
(value of F032)
and
recovery pressure 2
(value of F033), the control
setting can be easily switched by external button opera-
tion in accordance with usage time on the load side.
During ordinary control, the LOAD light is lit when load-
ing and goes off when unloading. With
pressure setting
2,
however, the light flashes when loading and goes off
when unloading.
For details, refer to page 24. (The
ECOMODE
however
cannot be used with
pressure setting 2.
)
29
3. OPERATING THE DSP [How to Use the Digital Monitor]
3.4.7 Pressure Setting Switch Function
Pressure setting 2 selection (flash range)
Ordinary (on range)
ON
OFF
External pressure setting switch
Time
Energy Saving Effect
Load
Unload
Start
pressure 2
Recovery
pressure 2
Start
pressure 1
Recovery
pressure 1
Line pressure
Load light
※
Start pressure = Cutout pressure
※