25
3. OPERATING THE DSP [How to Use the Digital Monitor]
3.4.2 How to Set Control Functions
■
Various settings (instantaneous power interruption (IPI), remote operation, capacity control
setting, pressure setting, etc.)
Switches display from monitor mode to setting mode (F mode).
1
1
2
1
2
リセット
表示切替
For details, see the F mode table.
To alter settings, change the values with the
buttons. ( page 26)
Displays 000
th
item of F mode.
Changes each time
FUNCTION
is pressed.
Forward
Back
Press
ENTER
to enter the settings.
Back
Press and hold
simultaneously for at
least 3 seconds.
Perform same
operation to return.
Displays setting contents.
F000:(0: Sets single unit operation.)
F000:(1: Sets multiple unit control.)
Settings can be altered or entered into the memory from the digital monitor without opening the start panel.
Function
7 segment
display
Item
Range
Precision/
unit
Initial value
Multiple unit control setting
F000
Control setting
0
〜
1
1
0
0
:
Single operation, 1: Multiple unit
control (communication supported)
Instantaneous power inter-
ruption (IPI) restart setting
F002
Instantaneous power inter-
ruption (IPI) setting
0
〜
1
1
0
0
:
ON
、
1
:
OFF
F003
Instantaneous power inter-
ruption (IPI) detection period
setting"
1
〜
5
1
1
When IPI is available, Instantaneous
power interruption is detected between
20ms and the setting detection period,
then the compressor restarts.
(
page 25)
Remote operation set-
ting
F005
Remote control switch
method
0
〜
3
1
0
0
:
Panel setting, 1
:
Local fi xed,
2
:
Remote fi xed,
3
:
Remote switch signal
F006
Remote operation method
0
〜
1
1
0
0
:
Pulse input, 1
:
Level input
F007
Remote operation shut-
down recovery
0
〜
1
1
0
0
:
Disable, 1
:
Enable
AUTO setting (
*
2)
F011
AUTO operation enable
0
〜
1
1
0
0
:
Enable, 1
:
Disable
Capacity control
F018
Control pressure selection
0
〜
2
1
0
0
:
Setting 1, 1
:
Setting 2,
2
:
External input
Function setting
(optional)
F021
Pressure control mode
0
〜
2
1
0
0
:
Built-in sensor, 1
:
External contact,
2
:
External input
Note:
※
Setting can be altered at any time other than this.
*
1
:
When set to 1,” history is cleared. After clearing, the value is automatically reset to “0.”
*
2
:
Only the V type is equipped with AUTO function. The AUTO function is available as an option for the Fixed speed type.
*
3
:
Refer to the below chart about the Pressure setting.
Don’t change the setting of digital monitor besides the above parameter F (7 segment display: F
***
).