Transport the products as close as possible to the installation location before unpacking.
Check the contents of the package:
-
DHWT Model
-
Installation and Operation Manual & Documents
11.1 SELECTION PROCEDURE FOR DHWT UNITS
C A U T I O N
• DHWT appliance is intended to be installed in an indoor
place.
• DHWT installation must be done by professional insta
-
llers.
• Install the DHWT with sufficient clearance around it for
operation and maintenance as shown in the following fi
-
gures.
• Install the DHWT where good ventilation is available. Do
not install the DHWT where there is a high level of oil
mist, salty air or sulphurous atmosphere.
• Working with no sufficient ventilation, in an enclosed
space, should cause oxygen deficiency. Toxic gas should
be produced when cleaning agent is heated to high tem
-
perature by, e.g., being exposed to fire.
• Do not install DHWT near any flammable substance.
• When installing some device next to DHWT, keep clearan
-
ce between DHWT and any other obstacle of more than
500mm.
11.2 WORKING SPACE
-
Check that DHWT are installed vertically.
-
For cleaning, use no flammable and no toxic cleaning liquid. The use of flammable agents should cause explosion or fire.
-
Cleaning liquid shall be collected after cleaning.
-
Pay attention do not trap cables when closing the electrical box cover. It could cause a electric shock.
11.3 WATER SUPPLY CONTROL WARRANTY
Well water or river water could, in most cases, contain suspended
solid matter, organic matter, and scales in big quantities. There
-
fore, the water should be subjected to a filtration process or to a
softener treatment by using chemical products before it’s applica
-
tion as a DHWT water.
It is also necessary to analyse the quality of the water by checking
pH, electrical conductivity and others.The following is the recom
-
mended standard water quality:
Item
DHWT Supply Water
Chlorine Ion (mg C1¯/1)
Less than 150
Electrical Condutivity (µs/cm)
100~2000
Total Hardness (mg CaCO3/1)
60~150
N O T E
Water range will be according s/UNE 112076:2004 IN.
11
Содержание DHWT200E-2.5H1E
Страница 2: ......
Страница 24: ......
Страница 42: ......
Страница 60: ......
Страница 78: ......
Страница 96: ......
Страница 114: ......
Страница 132: ......
Страница 150: ......
Страница 168: ......
Страница 186: ......
Страница 187: ......
Страница 188: ...PMML0198A rev 1 04 2011 Printed in Spain ...