Example 4
1- PC-ARFH2E attached into the unit and used as unit controller and room thermostat for both zones.
2- Wired room sensor for Zone 1
3- Wired room sensor for Zone 2
Indoor unit
1
Living room Zone 1
Bedroom Zone 2
Order
FIRST
Type
Main
Unit + Circuits
Questions
Answers
Is this device attached to the unit?
YES
Is this device used as a Room Thermostat of a zone?
YES, IN BOTH ZONES
Which are the heat emitters of circuit 1?
Underfloor heating
Which are the heat emitters of circuit 2?
Underfloor heating
Which are the cool emitters of circuit 1?
-
Which are the cool emitters of circuit 2?
-
Do you have domestic hot water tank?
NO
Do you have swimming pool?
NO
Do you have boiler?
NO
Do you have electric backup heater?
NO
COMPLETED
?
N O T E
•
After finishing Configuration assistant, go to Input&Outputs&Sensor menu and select which auxiliary sensor do you want to use for ambient
temperature in each zone.
• Example:
REF
Access
Description
Default Value
Selected value
Auxiliary Sensors
Taux1
Sensor 1 (Taux1)
Two3 (if Boiler)
C1 Ambient
Taux2
Sensor 2 (Taux2)
Swimming pool (if SWP existing)
C2 Ambient
Taux3
Sensor 3 (Taux3)
Outdoor Sensor
-
UNIT CONTROLLER
PMML0575 rev.1 - 09/2021