Split system - Indoor unit
YUTAKI S
Model
Power supply
Operation mode
Max.
current
(A)
Power supply
cables
Transmitting
cables
Actuator
cables
EN60335-1
EN60335-1
EN60335-1
RWM-(2.0-3.0)R1E
1~ 230V 50Hz
Without electric heaters
0.63
2 x 0.75 mm² + GND
2 x 0.75 mm
2
(Shielded
cable)
2 x 0.75
mm
2
+ GND
With electric heater
13.7
2 x 2.5 mm² + GND
With DHW tank heater
13.7
2 x 2.5 mm² + GND
With electric and DHW tank heaters
26.7
2 x 6.0 mm² + GND
RWM-(2.0-3.0)R1E
3N~ 400V 50Hz
Without electric heaters
0.6
4 x 0.75 mm² + GND
With electric heater
5.0
4 x 2.5 mm² + GND
With DHW tank heater
13.7
4 x 4.0 mm² + GND
With electric and DHW tank heaters
18.0
4 x 6.0 mm² + GND
RWM-(4.0-6.0)N1E
1~ 230V 50Hz
Without electric heaters
0.7
2 x 0.75 mm² + GND
With electric heater
26.7
2 x 6.0 mm² + GND
With DHW tank heater
13.7
2 x 2.5 mm² + GND
With electric and DHW tank heaters
39.8
2 x 10.0 mm² + GND
3N~ 400V 50Hz
Without electric heaters
0.7
4 x 0.75 mm² + GND
With electric heater
9.3
4 x 2.5 mm² + GND
With DHW tank heater
13.7
4 x 2.5 mm² + GND
With electric and DHW tank heaters
22.4
4 x 6.0 mm² + GND
RWM-(8.0/10.0)N1E
3N~ 400V 50Hz
Without electric heaters
0.7
4 x 0.75 mm² + GND
With electric heater
13.7
4 x 4.0 mm² + GND
With DHW tank heater
13.7
4 x 4.0 mm² + GND
With electric and DHW tank heaters
26.7
4 x 10.0 mm² + GND
?
N O T E
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
ELECTRICAL AND CONTROL SETTINGS
PMML0575 rev.1 - 09/2021