108 Chapter
5
Planning for Installation and Operation
Table 5.13 Floor Load Rating for 9960 Controller with Maximum Configuration
Required clearance (a+b)
Clearance (C) in meters (feet)
Floor Load Rating
kg/m
2
(lb/ft
2
)
C = 0
C = 0.2 (0.66)
C = 0.4 (1.31)
C = 0.6 (1.97)
C = 1.0 (3.28)
500 (102.4)
0.2 m (0.66 ft)
0
0
0
0
450 (92.2)
0.9 m (3 ft)
0.3 m (1 ft)
0
0
0
400 (81.9)
1.8 m (5.9 ft)
1.1 m (3.6 ft)
0.6 m (2 ft)
0.2 m (0.66 ft)
0
350 (71.7)
3.2 m (10.5 ft)
2.4 m (7.9 ft)
1.7 m (5.6 ft)
1.1 m (3.6 ft)
0.3 m (1 ft)
300 (61.4)
5.4 m (17.7 ft)
4.3 m (14.1 ft)
3.4 m (11.2 ft)
2.7 m (8.9 ft)
1.6 m (5.2 ft)