5.3.5
Input Voltage Tolerances
Table 5.6 lists the input voltage tolerances for the single-phase 9900 subsystem. Transient
voltage conditions must not 15-18% of nominal and must return to a steady-state
tolerance of b6 and -8% of the normal related voltage in 0.5 seconds or less. Line-
to-line imbalance voltage must not exceed 2.5%. Nonoperating harmonic contents must not
exceed 5%.
Table 5.6
Input Voltage Specifications for Single-Phase Power
Frequency
Input Voltages (AC)
Wiring
Tolerance(%)
60 Hz
±
0.5 Hz 200V, 208V or 230V
Single-phase two wire + ground +6% or -8%
50 Hz
±
0.5 Hz 200V, 220V, 230V or 240V Single-phase two wire + ground +6% or -8%
Note:
User input requires a 20-amp circuit breaker for single-phase power.