![Hitachi 9900 Series Скачать руководство пользователя страница 128](http://html.mh-extra.com/html/hitachi/9900-series/9900-series_user-and-reference-manual_143247128.webp)
114 Chapter
5
Planning for Installation and Operation
5.7.5
Vibration and Shock Tolerances
Table 5.21 lists the vibration and shock tolerance data for the 9900 subsystem. The 9900 can
be subjected to vibration and shock up to these limits and still perform normally. The user
should consider these requirements if installing the 9900 near large generators located on
the floor above or below the 9900 subsystem. Generators or any other source of vibration, if
not insulated or shock-mounted, can cause excessive vibration that may affect the
subsystem.
Table 5.21 Vibration and Shock Tolerances
Condition Operating
Nonoperating
Shipping or Storage
Vibration
0.01” (0.25 mm), 5~10 Hz
0.05
g
, 10~300 Hz
0.1” (2.5 mm), 5~10 Hz
0.5
g
, 10 to 70 Hz
0.002” (0.05 mm), 70~99 Hz
1.0
g
, 99 to 300 Hz
0.5
g
, 15 min.
*1
At four most severe resonance frequencies
between 5 to 200 Hz
Shock
—
- 8
g
, 15 ms
Horizontal: Incline Impact 4 ft (1.22 m)
*2
Vertical: Rotational Edge 0.3 ft (0.1 m)
*3
*1
: See ASTM D999-86, Standard Methods for Vibration Testing of Shipping Containers.
*2
: See ASTM D880-86, Standard Methods of Incline Impact Test for Shipping Containers.
*3
: See ASTM D775-80, Standard Methods for Drop Test for Loaded Boxes.
g
= acceleration equivalent to gravity (9.8 m/sec
2
)
Содержание 9900 Series
Страница 1: ...Hitachi Freedom Storage Lightning 9900 User and Reference Guide ...
Страница 2: ......
Страница 6: ...vi Preface ...
Страница 14: ...xiv Contents ...
Страница 42: ...28 Chapter 2 Subsystem Architecture and Components ...
Страница 132: ...118 Chapter 6 Troubleshooting ...
Страница 134: ...120 Appendix A Unit Conversions ...