ELECTRICAL WIRING
PMML0293A rev.2 - 08/2016
15
8.2.3 Terminal board connection and remarks
Control box
Terminal board 1
Mark
Item
Name
Description
Wire and maximum current
specification (EN60335-1)
¦
1
V+
DUTY V: Duty control by voltage (0~10V) (0~5V) (optional):
V+: Output power to device (+24Vdc)
Wire section: 3x0,5 mm
2
?
N O T E
Maximum power by 24Vdc output: 3 W
2
D
D: Voltage input (0~10V) (0~5V)
3
N
N: GND
§
4
1
CO
2
signal (optional):
Free contact: By closing the signal, the fan speed is set to High mode.
Wire section: 2x0,5 mm
2
5
2
¨
6
T
EC1: PWM Output control for EC FAN 1 (optional):
T: Tach input signal (Hz)
Wire section: 3x0,5 mm
2(1)
7
P
P: PWM output signal (0-100%)
8
G
G: GND
©
9
T
EC2: PWM Output control for EC FAN 2 (optional):
T: Tach input signal (Hz)
Wire section: 3x0,5 mm
2(1)
10
P
P: PWM output signal (0-100%)
11
G
G: GND
ª
12
V+
DUTY A: Duty control by current (4~20mA) (optional):
V+: Output power to device (+24Vdc)
Wire section: 3x0,5 mm
2
?
N O T E
Maximum power by 24Vdc output: 3 W
13
D
D: Current input (4~20 mA)
14
N
N: GND
«
15
1
FS: Flow switch (optional):
Free contact between terminals 1(15) and 2(16)
Wire section: 2x0,5 mm
2
16
2
¬
17
1
CONTROL: H-LINK and remote controller comunication (Necessary):
The H-LINK transmission between outdoor unit and indoor unit is 2 wired to
terminals 1-2.
Wire section: 2x0,5mm
2
18
2
19
A
The Remote controller must be connected between pins A and B
(non polarity)
Wire section: 2x0,5 mm
2
20
B
?
N O T E
(*1): If fan wiring length is higher than 3m, use shielded wires in compliance with local codes.
ENGLISH
Содержание 7E610900
Страница 1: ...DX Interface EXV 2 0 10 0 E2 ...
Страница 2: ......
Страница 8: ......
Страница 57: ......