REFRIGERANT PIPING AND CHARGE
PMML0293A rev.2 - 08/2016
12
Table of values for area boundaries
DX-Interface HP
Concept
2 HP
2.5 HP
3 HP
4 HP
5 HP
6 HP
8 HP
10 HP
A
HEX Volume [dm
3
]
0.57
0.89
1.03
1.51
1.92
1.92
2.92
3.89
Pipe length [m]
50
50
50
75
75
75
100
100
A’
HEX Volume [dm
3
]
0.57
0.89
1.03
1.51
1.92
1.92
2.92
3.89
Pipe length [m]
30
30
30
30
30
30
30
30
B
HEX Volume [dm
3
]
1.16
1.35
1.57
2.37
2.37
2.92
3.89
4.76
Pipe length [m]
50
50
50
75
75
75
100
100
B’
HEX Volume [dm
3
]
1.16
1.35
1.57
2.37
2.37
2.92
3.89
4.76
Pipe length [m]
30
30
30
30
30
30
30
30
C
HEX Volume [dm
3
]
1.4
1.59
2.23
3.03
3.03
3.58
4.55
6.06
Pipe length [m]
30
30
30
55
55
55
80
80
C’
HEX Volume [dm
3
]
1.4
1.59
2.23
3.03
3.03
3.58
4.55
6.06
Pipe length [m]
10
10
10
10
10
10
10
10
D
HEX Volume [dm
3
]
1.64
1.83
2.89
3.9
3.9
4.45
6.27
9.43
Pipe length [m]
10
10
10
30
30
30
30
30
E
HEX Volume [dm
3
]
-
-
-
4.56
4.56
5.11
6.93
10.73
Pipe length [m]
-
-
-
10
10
10
10
10
α
-
0.03
0.03
0.04
0.06
0.06
0.06
0.06
0.12
β
-
1.26
L_0 [m]
-
30m if HEX Volume ≤ V
B’
Interpolation with points V
B’
& V
C’
if V
B’
< HEX Volume < V
C’
10m if HEX Volume ≥ V
C’
V_0 [dm
3
]
-
1.16
1.35
1.57
2.37
2.37
2.92
3.89
4.76
7.5 CYCLE DESIGN EVAPORATING AND CONDENSING TEMPERATURES
Please make sure that the Heat Exchanger element to be connected to the DX-Interface series 2 satisfies the following installation
and design requirements. Failure to satisfy any of the items below may cause unappropriated system response, malfunction of any
of the system components, and/or damage to the components..
-
The design pressure of the system is 4.15 MPa. The compression strength of the pipes must exceed 12.45 MPa (3 times the
design pressure)
-
The inner volume of the heat exchanger piping must be within the limits specified in the technical documentation of each
DX-Interface series 2. Please make sure the design of the heat exchanger as well as the refrigerant charge follow such
limitations.
-
The capacity of the heat exchanger must meet the specified nominal capacity of each DX-Interface series 2 under the
following temperature conditions. Failure to ensure heat exchanger capacity may lead to system malfunction.
Design temperatures
Heating
Design temperatures
Cooling
Air temperature:
DX-interface HEX (T
in
): 20ºC(DB)
Outdoor: 7ºC(DB)/6ºC(WB)
Air temperature:
DX-Interface HEX (T
in
):
27ºC(DB)/19ºC(WB)
Outdoor: 35ºC(DB)
Condensing Temperature:
40ºC ~ 45ºC
Evaporation Temperature:
6ºC
Subcooling Temperature:
3ºC
Superheating Temperature:
5ºC