UNIT INSTALLATION
PMML0293A rev.2 - 08/2016
8
6.4 THERMISTOR INSTALLATION
Liquid and gas pipes thermistors
Two type thermistors are supplied inside the control box. The
purpose and identification of each one is as follow:
Item
PCB socket
/ Thermistor
connector color
PCB
socket
number
Thermistor
length (mm)
Liquid pipe thermistor
Black
THM 3
650
Gas pipe thermistor
Yellow
THM 5
600
!
C A U T I O N
In case that the thermistors supplied with the DX-Interface are not long
enough, please make sure that the length extension is properly done
avoiding the sensing distortion and that the joint is properly insulated to
avoid any electrical failure.
?
N O T E
When fitting the thermistors, remember that they must be secured
correctly by the special clamp, ensuring the perfect contact between the
pipe and thermistor. Cover it completely with insulation, like cork tape
or pipe insulation, depending on the location. Replace them if damaged
during maintenance work.
Thermistor installation example
1
Liquid / gas pipe thermistor (factory
supplied)
2
3
4
1
2
Thermistor holder (field supplied)
3
Thermistor lead wire (field supplied)
4
Insulation (field supplied)
!
C A U T I O N
The thermistor must be installed properly in order to avoid water onto the
thermistor.
Typical installation location
A Liquid pipe
thermistor
Must be installed in the
coldest liquid line point in
the heat exchanger
(prior the distributor).
A
B
B Gas pipe
thermistor
Must be installed as close
as possible to the heat
exchanger refrigerant
outlet.
Air thermistor
Two air thermistors are supplied inside the control box. The
purpose and identification of each one is as follow:
Item
PCB socket
/ Thermistor
connector color
PCB socket
number
Thermistor
length (mm)
Inlet air thermistor
Blue
THM 1
1200
Outlet air thermistor
Red
THM 2
1200
!
C A U T I O N
In case that the thermistors supplied with the DX-Interface are not long
enough, please make sure that the length extension is properly done
avoiding the sensing distortion and that the joint is properly insulated to
avoid any electrical failure.
?
N O T E
When fitting the air thermistor, remember that they must be secure
correctly, in an adequate place to avoid external influences, like ambient
conditions, and where the air temperature is significant.
Cable clamp example
1
Tie (Field supplied)
3
2
Cable clamp (Field supplied)
3
Thermistor (supplied)
!
C A U T I O N
The thermistor must be installed properly in order to avoid water onto the
thermistor.
Typical installation
In case of modular outdoor unit installation, it is possible to install air
thermistors only to the DX-Interface set as “group controller”. The
thermistors locations must ensure then a proper reading of the air
temperature, representative of the total inlet or outlet air flows of the unit
to be controlled.
?
N O T E
In case of simplified air thermistors installation, only one Remote
Controller can be connected within the DX-Interface gruped together and
connected to the same indoor unit (the installations of a second remote
controller is allowed only if it is set as “slave”)
Thermistor extension installation
A
B
A
B
PCB socket
Thermistor
extension
Thermistor
extension
Thermistor
THM1
Blue
Blue
Blue
THM2
Red
Red
Red
THM3
Black
Black
Black
THM5
Yellow
Yellow
Yellow