47
Precise Measurement for Earth Resistance
(Precise Measurement Method,
3-pole Method)
• The auxiliary earthing electrodes’ earth resistance (R
S
, R
H
)
measured values are used to automatically check whether the
earthing electrode’s earth resistance (R
E
) can be measured. R
S
and R
H
do not provide the same level of resolution as the earthing
electrode’s earth resistance (R
E
).
For the resolution of earth resistance of auxiliary earthing
electrode, see “Specifications” (p. 67).
• When the resistance (R
H
) of auxiliary earthing electrode exceeds
5 k
Ω
, the display range becomes the range of 200
Ω
without
displaying the digit of 0.01
Ω
even though the resistance of
earthing electrode is 20
Ω
or less. The following table shows
examples.
If the digit of 0.01
Ω
is required, pour some water over the
auxiliary earthing rod (H) to reduce the earth resistance to 5 k
Ω
or less.
Resistance RH of
auxiliary earthing
electrode H
Example of indicated
value (1)
When 9.52
Ω
is
measured
Example of indicated
value (2)
When 13.48
Ω
is
measured
0 to 5 k
Ω
9.52
Ω
(Range: 20
Ω
)
13.48
Ω
(Range: 20
Ω
)
5 k
Ω
to 50 k
Ω
9.5
Ω
(Range: 200
Ω
)
13.5
Ω
(Range: 200
Ω
)
HIOKI FT6031B961-00
Содержание FT6031-50
Страница 2: ...HIOKI FT6031B961 00...
Страница 6: ...iv Contents HIOKI FT6031B961 00...
Страница 20: ...14 Usage Notes HIOKI FT6031B961 00...
Страница 25: ...19 Part Names and Functions Operation buttons 1 2 3 4 6 7 5 HIOKI FT6031B961 00...
Страница 90: ...84 Error Display HIOKI FT6031B961 00...
Страница 94: ...88 Measurement Principle HIOKI FT6031B961 00...
Страница 95: ...HIOKI FT6031B961 00...
Страница 96: ...HIOKI FT6031B961 00...
Страница 97: ...HIOKI FT6031B961 00...