4 Start-up
X-HART 32 01
Page 40 of 58
HI 801 307 E Rev. 5.00
4.3.2
Tab: I/O Submodule HART_32_01
The
I/O Submodule HART_32_01
tab contains the following system parameters:
Name
R/W
Description
These statuses and parameters are entered directly in the Hardware Editor.
Name
W
Module name
HART ID
The HART ID corresponds to the IO Card Number when
addressing field devices using HART command 77.
Range of values: 0...249
Standard: 0
X-COM
Selection of the COM module within which HART over IP
is processed.
Name
Data type R/W
Description
The following statuses and parameters can be assigned global variables and used in the user program.
Diagnostic Request
DINT
W
To request a diagnostic value, the appropriate ID must be
sent to the module using the parameter
Diagnostic
Request
(see Chapter 5.3.5 for coding details).
Diagnostic Response
DINT
R
As soon as
Diagnostic Response
returns the ID of
Diagnostic Request
(see 5.3.5 for coding details),
Diagnostic Status
contains the diagnostic value
requested.
Diagnostic Status
DWORD
R
Requested diagnostic value in accordance with
Diagnostic Response.
The IDs of
Diagnostic Request
and
Diagnostic Response
can be evaluated in the user program.
Diagnostic Status
only contains the requested diagnostic value when both
Diagnostic Request and Diagnostic Response have the
same ID.
HART: Allow Device-
Specific Commands
BOOL
W
TRUE: Allow Device-Specific Commands
FALSE: Lock Device-Specific Commands
If the lock is active (FALSE), the following
device-specific
commands
are not forwarded to the HART field device:
(77, 128…253) and all the commands between 0 and
65535 that are not specified as read or write commands
in this table.
HART: Allow Read
Commands
BOOL
W
TRUE: Allow universal common practice read command
FALSE: Lock universal common practice read command
If the lock is active (FALSE), the following read
commands are not allowed:
(0, 1, 2, 3, 7, 8, 9, 11, 12, 13, 14, 15, 16, 20, 21, 48, 33,
50, 54, 57, 60, 61, 62, 63, 70, 72, 73, 74, 75, 76, 77, 78,
80, 81, 84, 85, 86, 90, 91, 93, 94, 95, 96, 98, 101, 105,
110, 114, 115, 512)