4 Start-up
X-HART 32 01
Page 38 of 58
HI 801 307 E Rev. 5.00
4.3
Configuring the Module in SILworX
The module is configured in the Hardware Editor of the SILworX programming tool.
Observe the following points when configuring the module:
Configure the corresponding analog input or output module in SILworX.
To diagnose the module and channels, the system parameters can be evaluated within the
user program. For more information on the system parameters, refer to the tables starting
with Chapter 5.3.
In case of analog output redundancy, the
Module Status
parameter must be additionally
taken into account, see HI 801 111 E.
If short-circuits or open-circuits occur, no HART communication is possible. Under these
conditions, the requests or settings performed through HART communication must be rejected.
To evaluate the statuses from within the user program, assign the module statuses global
variables. Perform this step in the Hardware Editor using the module's detail view.
The following tables present the statuses and parameters for the module in the same order
given in the Hardware Editor.
TIP
To convert hexadecimal values to bit strings a scientific calculator such as the Windows
®
calculator with the corresponding view can be used.