3 Product Description
X-HART 32 01
Page 26 of 58
HI 801 307 E Rev. 5.00
3.6.4.2
Terminal Assignment for Mono Connector Boards with Screw Terminals
Pin no.
Designation
Signal
Pin no.
Designation
Signal
1
01a
AO1+
1
02a
AO2+
2
01b
AO1-
2
02b
AO2-
3
03a
AO3+
3
04a
AO4+
4
03b
AO3-
4
04b
AO4-
5
05a
AO5+
5
06a
AO6+
6
05b
AO5-
6
06b
AO6-
7
07a
AO7+
7
08a
AO8+
8
07b
AO7-
8
08b
AO8-
Pin no.
Designation
Signal
Pin no.
Designation
Signal
1
09a
AO9+
1
10a
AO10+
2
09b
AO9-
2
10b
AO10-
3
11a
AO11+
3
12a
AO12+
4
11b
AO11-
4
12b
AO12-
5
13a
AO13+
5
14a
AO14+
6
13b
AO13-
6
14b
AO14-
7
15a
AO15+
7
16a
AO16+
8
15b
AO15-
8
16b
AO16-
Table 14: Terminal Assignment for Mono Connector Boards with Screw Terminals
Cable plugs attached to the connector board pin headers are used to connect to the field zone.
The cable plugs feature the following properties:
Connection to the field zone
Cable plugs
4 pieces, with 8 poles
Wire cross-section
0.2…1.5 mm
2
(single-wire)
0.2…1.5 mm
2
(finely stranded)
0.2…1.5 mm
2
(with wire end ferrule)
Stripping length
6 mm
Screwdriver
Slotted 0.4 x 2.5 mm
Tightening torque
0.2…0.25 Nm
Table 15: Cable Plug Properties