X-HART 32 01
3 Product Description
HI 801 307 E Rev. 5.00
Page 27 of 58
3.6.4.3
Terminal Assignment for Redundant Connector Boards with Screw Terminals
Pin no.
Designation
Signal
1
01a
AO1+
2
01b
AO1-
3
03a
AO3+
4
03b
AO3-
5
05a
AO5+
6
05b
AO5-
7
07a
AO7+
8
07b
AO7-
Pin no.
Designation
Signal
1
09a
AO9+
2
09b
AO9-
3
11a
AO11+
4
11b
AO11-
5
13a
AO13+
6
13b
AO13-
7
15a
AO15+
8
15b
AO15-
Table 16: Terminal Assignment for Redundant Connector Boards with Screw Terminals
Cable plugs attached to the connector board pin headers are used to connect to the field zone.
The cable plugs feature the following properties:
I/O lines
Cable plugs
2 pieces, with 8 poles
Wire cross-section
0.2…1.5 mm
2
(single-wire)
0.2…1.5 mm
2
(finely stranded)
0.2…1.5 mm
2
(with wire end ferrule)
Stripping length
6 mm
Screwdriver
Slotted 0.4 x 2.5 mm
Tightening torque
0.2…0.25 Nm
Table 17: Cable Plug Properties