X-HART 32 01
HIMax
®
HART Communication Module
Manual
Страница 1: ...X HART 32 01 HIMax HART Communication Module Manual...
Страница 2: ...A directly HIMA appreciates any suggestion on which information should be included in the manual Equipment subject to change without notice HIMA also reserves the right to modify the written material...
Страница 3: ...2 Indicators 13 3 4 3 Module Status Indicators 14 3 4 4 System Bus Indicators 15 3 4 5 I O indicators 15 3 5 Product Data 16 3 6 Connector Boards 18 3 6 1 Mechanical Coding of Connector Boards 18 3 6...
Страница 4: ...dule 44 4 4 2 HART Module with Redundant Analog Input Modulesn 45 4 4 3 HART Module with Analog Output Module 46 4 4 4 HART Module with Redundant Analog Output Modules 47 5 Operation 48 5 1 Handling 4...
Страница 5: ...HIMax System Manual Hardware description of the HIMax system HI 801 001 E HIMax Safety Manual Safety functions of the HIMax systems HI 801 003 E HIMax Communication Manual Description of communicatio...
Страница 6: ...ed 1 3 1 Safety Notes The safety notes are represented as described below These notes must absolutely be observed to reduce the risk to a minimum The content is structured as follows Signal word dange...
Страница 7: ...ge 7 of 58 1 3 2 Operating Tips Additional information is structured as presented in the following example i The text corresponding to the additional information is located here Useful tips and tricks...
Страница 8: ...ent type Range of values Protection class Protection class III in accordance with IEC EN 61131 2 Ambient temperature 0 60 C Storage temperature 40 85 C Pollution Pollution degree II in accordance with...
Страница 9: ...he user program Faults in the wiring 2 3 Safety Precautions Observe all local safety requirements and use the protective equipment required on site 2 4 Emergency Information A HIMax controller is a pa...
Страница 10: ...L 3 IEC 61508 IEC 61511 and IEC 62061 as well as Cat 4 and PL e EN ISO 13849 1 Refer to the HIMax Safety Manual HI 801 003 E for more information on the standards used to test and certify the module a...
Страница 11: ...label specifies the following important details Product name Mark of conformity Bar code 2D or 1D code Part number Part No Hardware revision index HW Rev Software revision index SW Rev Operating volt...
Страница 12: ...I O module controls and monitors the I O level The data and states of the I O module are made available to the processor modules via the redundant system bus The system bus has a redundant structure f...
Страница 13: ...X HART 32 01 3 Product Description HI 801 307 E Rev 5 00 Page 13 of 58 3 4 2 Indicators The following figure shows the LED indicators for the module Figure 3 Indicators...
Страница 14: ...ata transfer Table 3 Blinking Frequencies of LEDs 3 4 3 Module Status Indicators These LEDs are located on the front plate on the upper part of the module LED Color Status Description Run Green On Mod...
Страница 15: ...bus module in slot 2 has been established No connection to a redundant processor module running in system operation A B Off Off Neither physical nor logical connection to the system bus modules in sl...
Страница 16: ...voltage 24 VDC 15 20 rP 5 SELV PELV Current input min 300 mA max 400 mA Operating temperature 0 60 C Storage temperature 40 85 C Humidity max 95 relative humidity non condensing Type of protection IP2...
Страница 17: ...x 100 F in parallel to the ohmic load Crosstalk channel to channel DC or 50 Hz and 60 Hz not detectable except for the range 0 3 150 kHz 70 dB Crosstalk group to group DC or 50 Hz and 60 Hz 70 dB Refr...
Страница 18: ...52 X AI 32 51 Redundant connector board with screw terminals X CB 016 53 X AI 32 51 Connector board with cable plug X CB 016 54 X AI 32 51 Redundant connector board with cable plug X CB 017 01 X AO 16...
Страница 19: ...e Coded I O modules can be plugged in to uncoded connector boards Uncoded I O modules cannot be plugged in to coded connector boards 3 6 2 Coding of X CB 016 and X CB 017 Connector Boards a7 a13 a20 a...
Страница 20: ...a 20b 20c 22a 22b 22c 24a 24b 24c 25a 25b 25c 27a 27b 27c 29a 29b 29c 31a 31b 31c 26a 26b 26c 28a 28b 28c 30a 30b 30c 32a 32b 32c 23c 01a 01b 01c 03a 03b 03c 05a 05b 05c 07a 07b 07c 02a 02b 02c 04a 04...
Страница 21: ...I8 Pin no Designation Signal Pin no Designation Signal 1 09a S9 1 10a S10 2 09b AI9 2 10b AI10 3 09c AI9 3 10c AI10 4 11a S11 4 12a S12 5 11b AI11 5 12b AI12 6 11c AI11 6 12c AI12 7 13a S13 7 14a S14...
Страница 22: ...AI31 11 32b AI32 12 31c AI31 12 32c AI32 Table 11 Terminal Assignment for Connector Boards with Screw Terminals Cable plugs attached to the connector board pin headers are used to connect to the fiel...
Страница 23: ...able Plug Mono Redundant X CB 016 03 X CB 016 04 X CB 016 53 X CB 016 54 cba X CB 016 x3 cba X CB 016 x4 3 4 2 1 5 HART Module Plug I O Module Plug Connection to the Field Zone Cable Plug in Row 1 Con...
Страница 24: ...AI26 BU 1 Not used 8 S25 PK 1 AI25 GY 1 Not used 9 S24 YE 1 AI24 GN 1 Not used 10 S23 BN 1 AI23 WH 1 Not used 11 S22 RD BK AI22 BU BK Not used 12 S21 PK BK AI21 GY BK Not used 13 S20 PK RD AI20 GY RD...
Страница 25: ...01 X CB 017 02 X CB 017 51 1 2 09a 09b 11a 11b 13a 13b 15a 15b 10a 10b 12a 12b 14a 14b 16a 16b 01a 01b 03a 03b 05a 05b 07a 07b 02a 02b 04a 04b 06a 06b 08a 08b X CB 017 x1 09a 09b 11a 11b 13a 13b 15a...
Страница 26: ...b AO10 3 11a AO11 3 12a AO12 4 11b AO11 4 12b AO12 5 13a AO13 5 14a AO14 6 13b AO13 6 14b AO14 7 15a AO15 7 16a AO16 8 15b AO15 8 16b AO16 Table 14 Terminal Assignment for Mono Connector Boards with S...
Страница 27: ...AO13 6 13b AO13 7 15a AO15 8 15b AO15 Table 16 Terminal Assignment for Redundant Connector Boards with Screw Terminals Cable plugs attached to the connector board pin headers are used to connect to t...
Страница 28: ...with Cable Plug Mono Redundant X CB 017 03 X CB 017 04 X CB 017 53 cba X CB 017 x3 cba X CB 017 04 1 3 4 2 5 HART Module Plug I O Module Plug Connection to the Field Zone Cable Plug in Row 1 Connectio...
Страница 29: ...1 D2B GN RD 5 Not used Not used 6 Not used Not used 7 Not used Not used 8 Not used Not used 9 Not used Not used 10 Not used Not used 11 Not used Not used 12 Not used Not used 13 Not used Not used 14 N...
Страница 30: ...used U1 D2B GN RD 5 Not used Not used 6 Not used Not used 7 Not used Not used 8 Not used Not used 9 Not used Not used 10 Not used Not used 11 Not used Not used 12 Not used Not used 13 Not used Not use...
Страница 31: ...Combustion behavior Flame resistant and self extinguishing in accordance with IEC 60332 1 2 2 2 Length 8 30 m Color coding Based on DIN 47100 see Table 13 Table 20 Cable Data Identical Cable Plugs Fig...
Страница 32: ...ior Flame resistant and self extinguishing in accordance with IEC 60332 1 2 2 2 Length 8 30 m Color coding Based on DIN 47100 see Table 18 and Table 19 Table 22 Cable Data Identical Cable Plugs Figure...
Страница 33: ...e Take the appropriate earthing measures when connecting the plugs and terminals to the field zone Use shielded cables with twisted pairs Connect one twisted pair of the shielded cable to each of the...
Страница 34: ...ss PH 1 or slotted 0 8 x 4 0 mm Matching connector board To install the connector board 1 Insert the connector board into the guiding rail with the groove facing upwards see following figure Fit the g...
Страница 35: ...ample of how to Secure the Mono Connector Board with Captive Screws i These instructions also apply for redundant connector boards The number of slots used varies in accordance with the connector boar...
Страница 36: ...rack Move the locks to the open position Lift the cover plate and insert into the fan rack 2 Insert the top of the module into the hook in rail see 3 Swivel the lower edge of the module towards the ba...
Страница 37: ...Removing a Module Swiveling a Module in and out Securing and Releasing a Module Figure 14 Mounting and Removing a Module i If the HIMax system is operating do not open the cover plate of the fan rack...
Страница 38: ...output redundancy the Module Status parameter must be additionally taken into account see HI 801 111 E If short circuits or open circuits occur no HART communication is possible Under these conditions...
Страница 39: ...No module fault FALSE Module fault Channel fault no external faults the module is not inserted Observe the Module Status parameter Module Status DWORD R Status of the module Coding Description 0x00000...
Страница 40: ...t see 5 3 5 for coding details Diagnostic Status contains the diagnostic value requested Diagnostic Status DWORD R Requested diagnostic value in accordance with Diagnostic Response The IDs of Diagnost...
Страница 41: ...st Error BOOL R TRUE Background test is faulty FALSE Background test is free of faults Restart on Error BOOL W Using the parameter Restart on Error each I O module that has switched off permanently du...
Страница 42: ...ardware Editor 4 3 4 Submodule Status DWORD Coding of the variable Submodule Status Coding Description 0x00000008 Fault detected while initializing the module 0x00000080 Chip select monitoring time 0x...
Страница 43: ...202 203 300 Comparator 24 V undervoltage BOOL 1001 1032 Status of the channels 1 32 Coding Description 0x0001 Error during internal tests see Chapter 5 3 4 0x0008 Internal fault occurred while contro...
Страница 44: ...dant to one another i Additionally a HART handheld can be configured for evaluation or set up purposes this HART handheld operates as secondary master and is connected in parallel to the transmitter a...
Страница 45: ...HART module are inserted in the base plate next to each other and on a common connector board Connector boards X CB 016 02 with screw terminals or X CB 016 04 with cable plug can be used S GND AI R A...
Страница 46: ...nnector boards X CB 017 01 with screw terminals or X CB 017 03 with cable plug can be used to perform the wiring such as described in Figure 15 AO1 AO1 Analog Output Module Connector Board Actuator Lo...
Страница 47: ...odules and the HART module are inserted in the base plate next to each other and on a common connector board Connector boards X CB 017 02 with screw terminals or X CB 017 04 with cable plug can be use...
Страница 48: ...orX documentation 5 2 Diagnosis LEDs on the front side of the module indicate the module state see Chapter 4 6 2 The diagnostic history of the module can also be read using SILworX Chapter 5 3 4 and C...
Страница 49: ...ously improving the operating system of the module HIMA recommends to use system downtimes to load the current version of the operating system into the module For detailed instructions on how to load...
Страница 50: ...7 Decommissioning X HART 32 01 Page 50 of 58 HI 801 307 E Rev 5 00 7 Decommissioning To decommission the module remove it from the base plate For more information see Mounting and Removing the Module...
Страница 51: ...oid mechanical damage HIMax components must be transported in packaging Always store HIMax components in their original product packaging This packaging also provides protection against electrostatic...
Страница 52: ...307 E Rev 5 00 9 Disposal Industrial customers are responsible for correctly disposing of decommissioned HIMax hardware Upon request a disposal agreement can be arranged with HIMA All materials must b...
Страница 53: ...X HART 32 01 9 Disposal HI 801 307 E Rev 5 00 Page 53 of 58...
Страница 54: ...tra Low Voltage PES Programmable Electronic System PFD Probability of Failure on Demand probability of failure on demand of a safety function PFH Probability of Failure per Hour probability of a dange...
Страница 55: ...r Boards with Cable Plug 28 Figure 10 System Cable X CA 001 01 n 31 Figure 11 System Cable X CA 011 01 n 32 Figure 12 Example of how to Insert the Mono Connector Board 34 Figure 13 Example of how to S...
Страница 56: ...nt for the System Cable Plug 24 Table 14 Terminal Assignment for Mono Connector Boards with Screw Terminals 26 Table 15 Cable Plug Properties 26 Table 16 Terminal Assignment for Redundant Connector Bo...
Страница 57: ...ge 57 of 58 Index block diagram 12 connector board 18 with screw terminals 25 with screw terminals 20 diagnosis 48 I O indicators 15 system bus indicators 15 module status indicators 14 safety functio...
Страница 58: ...aul Hildebrandt GmbH Co KG HIMax and SILworX are registered trademark of HIMA Paul Hildebrandt GmbH Co KG Albert Bassermann Str 28 68782 Br hl Germany Phone 49 6202 709 0 Fax 49 6202 709 107 HIMax inf...