F31 02
4 Start-Up
HI 800 147 E Rev. 1.01
Page 37 of 48
4.4.4
Digital Outputs for F31 02
System Signal
R/W
Description
Mod.SRS [UDINT]
R
Slot number (System Rack Slot)
Mod. Type [UINT]
R
Type of module, target value: 0x00B4 [180
dec
]
Mod. Error Code
[WORD]
R Module
error
code
Coding
Description
0x0000
I/O processing, if required with errors, see other error
codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: wrong configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not plugged in
DO.Error Code
[WORD]
R
Error codes for all digital outputs
Coding
Description
0x0001
Fault within the digital outputs
0x0002
MOT test of safety shutdown returns a fault
0x0004
MOT test of auxiliary voltage returns a fault
0x0008
FTT test of test pattern faulty
0x0010
MOT test of output switch test pattern faulty
0x0020
MOT test of output switch test pattern (shutdown test
of the outputs) faulty
0x0040
MOT test active shutdown via WD faulty
0x0200
All outputs are switched off, total current exceeded
0x0400
FTT test: 1st temperature threshold exceeded
0x0800
FTT test: 2nd temperature threshold exceeded
0x1000
FTT test: Monitoring of auxiliary voltage 1:
Low voltage
DO[xx].Error Code
[BYTE]
R
Error codes for the digital output channels
Coding
Description
0x01
Fault in the digital output module
0x02
Channel shutdown due to overload
0x04
Error while reading back the digital outputs
0x08
Error while reading back the status of the digital
outputs
DO[xx].Value
[BOOL]
W
Output value for DO channels:
1 = output energized
0 = output de-energized
Pulsed outputs must not be used as safety-related outputs!
Table 23: ELOP II Factory - Digital Output System Signals