F31 02
4 Start-Up
HI 800 147 E Rev. 1.01
Page 31 of 48
4.3.2.2
DO 20: Channels
Tab
The
DI 20: Channels
tab contains the following system parameters.
System parameter
Data
type
R/W Description
Channel no.
---
R
Channel number, defined by default
-> Error Code
[BYTE]
BYTE
R
Error codes for the digital input channels
Coding
Description
0x01
Fault in the digital input module
0x10
Short-circuit of the channel
0x80
Intermittence between pulsed output DO
and digital input DI, e.g.,
Open-circuit
Open
switch
L+ low voltage
-> Value [BOOL]
BOOL
R
Input values for the digital input channels
0 = input de-energized
1 = input energized
Pulse Channel
[USINT] ->
USINT
W
Source channel for pulsed supply
Coding
Description
0 Input
channel
1
Pulse of the 1st DO channel
2
Pulse of the 2nd DO channel
… …
8
Pulse of the 8th DO channel
Table 19: SILworX - System Parameters for the Digital Inputs,
DI 20: Channels
Tab
Содержание HIMatrix F31 02
Страница 47: ......