3 Product Description
F31 02
Page 22 of 48
HI 800 147 E Rev. 1.01
3.4.2.2
Network Ports Used for Ethernet Communication
UDP ports
Use
8000
Programming and operation with the programing tool
8001
Configuration of the remote I/O using the PES (ELOP II Factory)
8004
Configuration of the remote I/O using the PES (SILworX)
6010 safe
ethernet
and OPC
123
SNTP (time synchronization between PES and remote I/O, PES and
external devices)
6005/ 6012
If TCS_DIRECT was not selected in the HH network
502
Modbus (can be modified by the user)
44818
EtherNet/IP session protocol for device identification
2222 EtherNet/IP
Data
Exchange
Table 10: Network Ports (UDP Ports) in Use
TCP ports
Use
502
Modbus (can be modified by the user)
xxx
TCP SR assigned by the user
44818
Ethernet/IP Explicit Messaging Services
Table 11: Network Ports (TCP Ports) in Use
3.4.3
Reset Key
The controller is equipped with a reset key. The key is only required if the user name or
password for administrator access is not known. If only the IP address set for the controller
does not match the PADT (PC), the connection can be established with a
Route add
entry
on the PC.
The key can be accessed through a small round hole located approximately 5 cm from the
upper left-hand side of the enclosure. The key is engaged using a suitable pin made of
insulating material to avoid short-circuits within the controller.
The reset is only effective if the controller is rebooted (switched off and on) while the key is
simultaneously engaged for at least 20 seconds. Engaging the key during operation has no
effect.
Properties and behavior of the controller after a reboot with engaged reset key:
Connection parameters (IP address and system ID) are set to the default values.
All accounts are deactivated except for the administrator default account with empty
password.
With COM operating system version 10.42 and beyond, loading a user program or
operating system with default connection parameters is inhibited!
The loading procedure is only allowed after the connection parameters and the account
have been configured on the controller and the controller has been rebooted.
After a new reboot without the reset key engaged, the connection parameters (IP address
and system ID) and accounts become effective.
Those configured by the user.
Those valid prior to rebooting with the reset key engaged, if no changes were
performed.