3 Product Description
F2 DO 8 01
Page 20 of 40
HI 800 157 E Rev. 1.01
3.5
Product Data
General
Response time
≥
20 ms
Ethernet interfaces
2 x RJ-45, 10/100BaseT (with 100 Mbit/s) with integrated switch
Operating voltage
24 VDC, -15 %...+20 %, w
ss
≤
15 %,
from a power supply unit with safe insulation in accordance with
IEC 61131-2.
Current input
max. 0.6 A
Fuse (external)
10 A time-lag
back-up battery
None
Operating
temperature
0 °C...+60 °C
Storage temperature
-40 °C...+85 °C
Type of protection
IP20
Max. dimensions
(without plug)
Width: 207 mm (with enclosure screws)
Height: 114 mm (with fixing bolt)
Depth: 86 mm (with earthing screw)
Weight 1.3
kg
Table 11: Product Data
Relay outputs
Relay types
for each channel
2 safety relays with forcibly guided contacts,
1 standard relay
Number of outputs
8 potential-free normally open contact
Switching voltage
≥
5 V,
≤
250 VAC / 250 VDC
Switching current
≥
10 mA,
≤
3 A
internally fused with 3.15 A
fuse breaking capacity: 100 A
Switching capacity AC
UL:
250 VAC at 6 A
TÜV:
max. 250 VA, cos
ϕ
≥
0.5, at max. 250 VAC
max. 625 VA, cos
ϕ
= 1, at max. 250 VAC
Switching capacity DC
(induction free)
UL:
24 VDC at 1 A with ohmic load
TÜV:
up to 30 VDC:
max. 90 W (3,.5 A)
up to 70 VDC:
max. 22 W (0.315 A)
up to 127 VDC: max. 25 W (0.25 A)
up to 250 VDC: max. 40 W (0.16 A)
(adjust external fusing)
Contact material
Silver alloy
Switching time
approx. 30 ms
Reset time
approx. 10 ms
Bounce time
approx. 15 ms
Product life
mechanical
electrical
≥
3 x 10
6
switching operations
≥
2.5 x 10
5
switching operations at ohmic full load and
≤
0.1
switching operations per second
Table 12: Specifications of the Relay Outputs