Setpoints and optimization parameters
The equipment parameters are configured and set by the manufacturer.
The setpoint is also factory set. The defaults, for the MT and LT versions, are given in pages Cab03 and Cbb03
(LT configuration). The regulation setpoint in the above pages is a single fixed value which controls the unit when
it is running as a standalone system.
This parameter can be modified to suit the final application.
If the unit is combined with a dedicated evaporator, the suction setpoint regulation is not
fixed, but rather floating
when serial communications with evaporator are available. Serial communications enable exchange of realtime
information between the main Hecu CO2 controller and the coldroom controller.
The floating
suction pressure
setpoint can vary over a configurable range. This range is indicated in page CAb04,
conforming with the limits set
in Cab02.
Make sure that all equipment panels are correctly positioned, closed, and secured.