Section 3: Description of the Equipment
Section 3: Description of the Equipment
The condensing units described in this document are designed for use in commercial refrigeration. These
condensing unit systems are intended for use in locations where heat can be released outside of the building in
which they are installed..
The condensing units are compact, low-noise systems that are also suitable for outdoor use.
The unit is designed and optimized to work with CO2 (R744).
The operating modes can be transcritical or subcritical depending on the conditions of the external environment.
The electronic control, with appropriate logics, allows the equipment to always operate in conditions of maximum
efficiency in different environmental conditions and cold demand. It also manages lubrication and any alarms by
signaling them on the electronic control terminal.
Depending on the model, for the condensing unit, units can be provided with a single fan-motor, or with a
double fan.
All models are equipped with the following refrigerator accessories:
• Compressor(s) driven by inverter
• Control valves
• Intermediate receiver
•
Dehydrating filter and liquid indicator
•
On-board gas cooler
• Electrical panel with relative electronic control
In low-temperature refrigeration models, a desuperheater (intercooler) is incorporated in the gas cooler battery.
All models also have a crankcase heater that prevents the accumulation of liquid in the lower area of the
compressor during downturn periods. The unit is always enclosed in a self-supporting housing made of steel
varnished with epoxy powder and is equipped with electrical equipment with a main disconnecting switch (the
power supply wire that must be connected to the switch is not supplied).
The following variants are possible:
•
Only for medium-temperature units
•
Only for low--temperature units