Generic Cabling System
The electronic fence system is composed of front-end fence, energizer, back-end control part
and other linkage equipment. The pulse host is the core of the control, transmission and detection of
the electronic fence system. it provides the pulse voltage to the front fence through the high-voltage
insulated wire, and transmits the alarm signal to the back-end control part for management. It is
scattered and installed in the perimeter, the energizer of the double defense area is placed every 150
≤ 300 meters, according to the length of the specific design protection area, generally installed in the
outdoor rain box.
The
energizer
connects AC 220V power source through centralized or nearby power
supply.
Wiring tips:
There are two wires are needed, one is a RVV, recommended RVV2*1.5 or above
specifications; the other is a RVVS or RVVSP, recommended RVVS2*1.0 or above
specifications. The wiring is as follows:
1. Groove 30cm down along the wall bottom of perimeter to bury two
φ
2.0 cm
PVC pipes (galvanized pipe is preferred) for signal wire and power wire.
2. Spare outlet wire when the pipe arrives at the
energizer
.
3. Signal wire and power wire go through the buried PVC pipes separately by the use
of punch to the
energizer
, and then set aside a distance (the length from the entrance of the pipe to
the energizer) to connect the energizer with the terminal back to the host control room.
4. Avoid pipe joints in the pipe during the wiring, otherwise joints should be
appeared in the outlet only.
5. PVC pipes are better to be underground for 30 cm, but
φ
50 mm galvanized pipe
is recommended to where has a large vehicle flow and buried at least 50 cm down in the earth to
avoid the failure caused by the compression on pipes.
6. Use the punch directly for the wiring if there has been a reserved pipe.
7. Connect to the nearby power supply to save costs. Signal wire should come back to
connect controller keyboard in the host control room after connecting each energizer around the
perimeter.
8. A proper distance is required between pipes of power wire and signal wire to avoid
the
interference.