Panic Alarm Station
User Manual
56
Type of zone detector.
Zone Type
-
Instant
Under the arming status, as long as the detector connected to the zone is triggered, the alarm
controller will immediately generate an alarm without delay.
-
Fire
The fire zone is a 24-hour alarm zone. When the fire zone is triggered, the external sounder will
give a fire alarm sound.
-
24H Silent Zone
Detectors working in this zone are on alert for 24 hours, and will not be affected by arming and
disarming operations. Once triggered, they will immediately transmit information to the
command center, but there is no alarm sound.
-
Disabled
No event will trigger an alarm.
Audio File
Select the zone audio file. Mute can be selected.
Upload Restored Alarm
After enabling, when the alarm is recovered, the report will be uploaded to the center.
4. Check the Link Relay, Linked Channel, etc.
5. (Optional) Click Copy to, copy the zone parameters to other zones.
6. Click Save.
Relay Settings
Steps
1. Click Device → Relay.
2. Click
to set relay parameters.
Output Delay
After the zone event is triggered, the relay will close the relay output after the output delay.
The setting range is 0 to 2000 seconds.
3. Click Save.
4. Check the relay, click ON or OFF to open or close the relay.
Auxiliary Power Output
Steps
1. Click Device → Auxiliary Power Output.
2. Enable Switch of Auxiliary Power Output.
3. Click Save.