User Manual of Thermal Network Positioning system
© Hikvision
53
The function of dynamic fire source detection can only be enabled for
camera 2.
Fire and Smoke Detection Mode:
1)
Select Fire or Smoke, and the system alarms when device is either triggered
by Fire Source Detection or Smoke Detection.
2)
Select Fire and Smoke, the system holds when device is triggered by Fire
Source Detection or Smoke Detection. When target is detected by both
rules, the system sends two alarms, otherwise, the system sends single
alarm.
3)
Select Double Confirm, the system alarms when device is both triggered by
Fire Source Detection and Smoke Detection.
4)
Select Specified Fire Source, and the system alarms when device is triggered
by fire source detection.
5)
Select Specified Smoke, and the system alarms when device is triggered by
smoke.
Detection Mode: Select detection mode as by Multiple Frame, and the system
alarms with high accuracy. Select detection mode as by Single Frame, and the
system alarms with short delay.
Fire Source Zoom Mode: In Auto mode, the system moves and locates at the fire
source, and then it zooms according to the predefined focus mode. To set the focus
mode, go to Configuration>Advanced Configuration>Image>Channel No.2>Focus
Mode.
Sensitivity: Range [1-100], the smaller the value is, the fire source of lower
temperature can be detected.
Dwell Time(s): Range [0-120]. You can set the dwell time of the positioning system
staying the position where detects the fire source when performing auto scan,
patrol, pattern, scheduled task, and park action.
Fire Source Zoom Ratio: Set the zoom ratio of the optical channel when it detects
the fire source. In Auto mode, the optical channel changes its zoom ratio until two
channels have the same field of view. In Manual mode, you can set the optical
zoom ratio.
Smoke Detection: Set the sensitivity of the smoke detection. The greater the value
is, the easier the alarm will be triggered. (reserved)
4.
Check the checkbox of Display Fire Source Frame on Stream to display a red frame
around the fire source on stream when fire occurs. (Optional)
5.
Check the checkbox to select the linkage method taken for the alarm input.
Refer to
Step 3 in Section 5.2.1 Configuring Motion Detection
. In the field of Other Linkage, you
can check the checkbox to enable the alarm output (The alarm output number varies
depending on device ability).
6.
Click
to save the settings.
Содержание DS-2TD8166-180ZE2F-V2
Страница 1: ...Thermal Bi spectrum Network Positioning System User Manual UD05158B...
Страница 143: ......