Cod
Meaning
Cause / Origin
Reset
A07
Anti freeze alarm
Digital input active anti freeze
probe
Manual
proceed with manual reset.
A08
Water flow alarm
Digital input active for AL06
duration.
Automatic
It turns to manual after 3 events in 1
hour.
A09
Compressor 1 thermal
protection alarm
Digital input active
Manual
the event expires, then proceed with
manual reset.
A10
Compressor 2 thermal
protection alarm
Digital input active
Manual
the event expires, then proceed with
manual reset.
A11
Condenser fan thermal
protection alarm
Digital input active
Manual
the event expires, then proceed with
manual reset.
A12
Defrost error alarm
Max defrost time
Automatic
with next proper defrost cycle.
Proceed with manual reset.
A13
Compressor 1 maintenance
warning
Running hour > CO14
Manual
Proceed with the hour reset procedure.
A14
Compressor 2 maintenance
warning
Running hour > CO15
Manual
Proceed with the hour reset procedure
A15
Water pump maintenance
Warning
Running hour warning
Manual
Proceed with the hour reset procedure
rtC
Clock alarm
Need to set the clock time
Manual
Set the clock and then proceed with
manual reset.
rtF
Clock alarm
Faulty clock control
Manual
Proceed with manual reset, if nothing
happens change the clock.
EE
EEPROM error alarm
Possible data losing
Manual
Proceed with manual reset., if nothing
happens the controller is locked, no regulation
available.
ACF1
Configuration alarm
Heat pump configured without
reversing valve
Automatic
After parameter proper debug.
ACF2
Configuration alarm
without condensing probe
control configuration
Automatic
After parameter proper debug.
ACF3
Configuration alarm
Two digital inputs having the
same function
Automatic
After parameter proper debug.
FErr
Functioning alarm
Two digital inputs activated at
the same time
Manual
after the alarm event expires, proceed
with manual reset.
AFr
Frequency alarm
The frequency of power supply
is out of range
Automatic
After the frequency becomes normal
Содержание LZT 05
Страница 1: ...HIGH EFFICIENCY AIR TO WATER HEAT PUMPS LZT SERIES TECHNICAL MANUAL ...
Страница 2: ...LZT High efficiency air to water heat pumps MTLZTGB REV 012008 2 ...
Страница 33: ......
Страница 34: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......