15
LDK
COOLING CAPACITY AND COMPRESSORS INPUT POWER
PA = Compressor input power
Input power
correction factor
0,7
0,8
0,9
1,0
1,1
1,2
1,3
1,4
5
6
7
8
9
10
11
12
13
14
15
PF = Cooling capacity
Cooli
ng ca
pacit
y correctio
n fac
tor
0,7
0,8
0,9
1,0
1,1
1,2
1,3
1,4
1,5
5
6
7
8
9
10
11
12
13
14
15
The cooling capacity and the compressors input power in different working conditions can be obtained by multiplying the nominal
values (PF, PA) with their respective correction factors. The diagram above indicates the correction factors; for each curve, the
relative ambient conditions, assuming that the difference between inlet and outlet cold water temperature is 5°C.
30°C
40°C
35°C
25°C
20°C
Ambient temperature 45°C
45°C
Ambient temperature 20°C
40°C
35°C
30°C
25°C
User water outlet temperature (°C)
User water outlet temperature (°C)