background image

LZT 

High efficiency air to water heat pumps

 

 

 

MTLZTGB  

REV.012008 

9

 

TECHNICAL CHARACTERISTICS 

 

The high efficiency LZT heat pump series have been especially designed for application with radiant floor heating systems or in 

those applications where it is necessary to have the highest maximum efficiency in heating mode. The units have been optimized for 

heating mode, they are able to produce water up to 60°C and they can operate down to -15°C ambient temperature. All models are 

supplied standard with reverse cycle valve for cold water production. 

 

Frame 

All LZT units are made from hot-galvanised thick sheet metal, painted with polyurethane powder enamel at 180°C to ensure the best 

resistance against the atmospheric agents. The frame is self-supporting with removable panels.  All screws and rivets for outdoor 

installations are in stainless steel. The colour of the units is RAL 7035. 

 

Refrigerant circuit 

The refrigerant gas used in these units is R407C. The refrigerant circuit is made by using international primary brands components 

and according to ISO 97/23 concerning welding procedures. The refrigerant circuit includes: 

sight glass, filter drier, double thermal expansion valves (one for cooling mode, one for heating mode) with external equalizer, 4 way 
reverse cycle valve, one way valves, liquid receiver, Schrader valves for maintenance and control, pressure safety device (according 

to PED regulation). Models starting from 09T are also supplied with an AISI316 stainless steel heat exchanger used as economizer 

and additional expansion valve for refrigerant vapour injection. 

 

Compressors 

The compressors used are 

high performance scroll type

, supplied with a special scroll design who enhance the efficiency of the 

refrigerant cycle at low ambient conditions. Units starting from model 09T, are also supplied with an additional heat exchanger used 

as economizer and a vapour injection system, used to enlarge the working range. The compressors are all supplied with crankcase 

heater and thermal overload protection by a klixon embedded in the motor winding. They are mounted in a separate chamber in 

order to be separated from the air stream. The crankcase heater is always powered when the compressor is in stand-by. The 
inspection is possible through the frontal panel of the unit that allow the maintenance of the compressors even if the unit is working.

 

 

Source heat exchanger 

The source heat exchangers are made of copper pipes and aluminium fins. The diameter of the copper pipes is 3/8” and the 

thickness of the aluminium fins is 0,1 mm. The tubes are mechanically expanded into the aluminium fins to improve the heat 
exchange factor. The geometry of these condensers guarantee a low air side pressure drop and then the use of low rotation (and low 

noise emission) fans. The source heat exchangers can be protected by a metallic filter to be installed on request. 

 

Fans 

The fans are axial type with aluminium aerofoil blades. They are statically and dynamically balanced and supplied complete of the 
safety fan guard according to EN 60335. They are mounted on the unit frame by interposition of rubber vibration dampers. The 

electric motors are all at 6 poles (about 900 rpm). The motors are directly driven with an integrated thermal overload protection. The 

protection class of the motors is IP 54. 

 

User heat exchangers 

The user heat exchangers are made of AISI 316 stainless steel braze-welded plates type. The use of these kind of heat exchangers 

allows a massive reduction of the refrigerant charge of the unit compared to the traditional shell-in-tube evaporators and also a 

reduction of the overall dimensions of the unit. The user heat exchangers are factory insulated with flexible close cell material and 

can be equipped with antifreeze heater (optional). Each heat exchanger is provided with a temperature sensor as antifreeze 
protection. 

 

Electric box 

The electric box is made according to electromagnetic compatibility norms CEE 73/23 and 89/336. The accessibility to the board is 

possible after removing the front panel of the unit. The protection degree is IP55. In all LZT units are installed, standard, the 
compressors sequence relay who disable the operation of the compressor in case the power supply phase sequence is not the 

correct one (scroll compressors in fact, can be damaged if they rotate reverse wise). The following components are also standard 

installed: main switch, magnetic-thermal switches (as a protection of pumps and fans), compressors fuses, control circuit automatic 

breakers, compressor contactors, fan contactors, pump contactors. The terminal board is supplied with voltage free contacts for 
remote ON-OFF , winter/summer change over and general alarm. 

 

Microprocessors 

All LZT units are supplied standard with microprocessor controls. The microprocessor controls the following functions: regulation of 

the water temperature, antifreeze protection, compressor timing, compressor automatic starting sequence, alarm reset. The control 

panel is supplied with display showing all operational icons. The microprocessor is set for automatic defrost (in case of operation in 
severe ambient conditions) and for summer/winter/domestic hot water change over (SW6 versions only). Upon request any 

microprocessor can be connected to a BMS system for the remote control and management. The technical department is available 

to study, together with the customer, different solutions using MODBUS; LONWORKS; BACNET or TREND protocols. 

Содержание LZT 05

Страница 1: ...HIGH EFFICIENCY AIR TO WATER HEAT PUMPS LZT SERIES TECHNICAL MANUAL ...

Страница 2: ...LZT High efficiency air to water heat pumps MTLZTGB REV 012008 2 ...

Страница 3: ... 2 Ambiente industriale Compatibilité électromagnétique Norme génériqué immunité Partie 2 Environnement industriel Electromagnetic compatibility Generic immunity standard Part 2 Industrial environment Flüssigkeitssammler Reciver Elektromagnetische Verträglichkeit Allgemeine Bestimmung über die Immunität Teil 2 industrieller Raum Elektromagnetisk kompatibilitet Immunitet Del 2 Generella fordringar ...

Страница 4: ...atteri Certificato n Cerificat n Certificate n Zertifikate N Certifikat n CE 1370 PED A1 HID001 07 ITA Si dichiara sotto la nostra responsabilità che le forniture sopra indicate sono conformi in ogni parte alle direttive CEE di cui al punto 1 Le forniture sono state prodotte collaudate e verificate con riferimento alle normative di cui al punto 2 Nous declarons sous notre responsabilité que les fo...

Страница 5: ...ower page 15 User heat exchanger water pressure drops page 16 Domestic hot water heat exchanger water pressure drops page 17 User circuit water pumps available static pressure page 18 Operation limits page 19 Corrections tables page 20 Sound Data page 20 Safety Device Setting page 21 Electric data page 21 Inspection page 21 Lifting and handling page 21 Location and minimum technical clearances pag...

Страница 6: ...ty and functionality of its products HOW TO KEEP THIS MANUAL The manual must be always with the unit it refers to It must be stored in a safe place away from the dust and moisture It must be accessible to all users who shall consult it any time they are in doubt on how to operate the equipment HIDROS SRL reserves the right to modify its products and related manuals without necessarily updating pre...

Страница 7: ...ry user must be perfectly knowledgeable about the functions of the equipment and its controls and must have read and understood the information container in this manual It s strictly forbidden to remove and or camper with any safety device Any routine or not routine maintenance operation shall be carried out when the equipment has been shut down disconnected from electric and pneumatic power sourc...

Страница 8: ... free movements Appropriate lighting of the work place shall be provided so as to allow the operator to carry out the required operations safely Poor or too strong lighting can cause risks Ensure that work places are always adequately ventilated and that aspirators are working in good condition and in compliance with the requirements of the laws in force PERSONAL PROTECTIVE EQUIPMENT When operatin...

Страница 9: ...e the heat exchange factor The geometry of these condensers guarantee a low air side pressure drop and then the use of low rotation and low noise emission fans The source heat exchangers can be protected by a metallic filter to be installed on request Fans The fans are axial type with aluminium aerofoil blades They are statically and dynamically balanced and supplied complete of the safety fan gua...

Страница 10: ...le this can not be obtained if the water tank is installed on the hot water inlet water side Water pump centrifugal type suitable for chilled water operation The pump is directly controlled by the microprocessor that controls its correct operation In the hydraulic circuit are also present the expansion vessel the safety valve and the eventual manual valves with fittings LZT LS LOW NOISE VERSION Th...

Страница 11: ... 28 1x 0 28 1x 0 28 1x 0 28 2 x 0 2 2 x 0 31 2 x 0 37 2 x 0 37 2 x 0 37 Scroll Scroll with economizer and vapour injection Compressor type n 1 1 1 1 1 1 2 2 2 Refrigerant circuit n 1 1 1 1 1 1 1 1 1 Sound power level 6 dB A 68 68 68 68 70 74 79 79 79 Sound pressure level 7 dB A 40 40 40 40 42 46 51 51 51 Water pump option kW 0 25 0 25 0 25 0 25 0 37 0 37 0 55 0 55 0 55 Water tank capacity option l...

Страница 12: ...C TWUC C W W Mod TAMB C 35 40 45 50 55 60 35 40 45 50 55 60 35 40 45 50 55 60 15 4 3 4 3 1 8 2 0 2 4 2 2 10 5 2 5 2 1 9 2 1 2 7 2 5 7 5 8 5 7 5 7 2 0 2 2 2 4 2 9 2 6 2 4 5 6 2 6 2 6 1 2 0 2 2 2 4 3 1 2 8 2 5 2 6 9 6 8 6 7 6 7 2 1 2 3 2 5 2 8 3 3 3 0 2 7 2 4 0 7 5 7 3 7 2 7 1 7 0 2 1 2 3 2 6 2 8 3 1 3 5 3 1 2 8 2 5 2 3 2 8 0 7 8 7 7 7 6 7 5 2 2 2 4 2 6 2 9 3 1 3 7 3 3 2 9 2 6 2 4 5 8 9 8 7 8 5 8 3 ...

Страница 13: ... 3 0 2 7 LZT 20 15 23 4 23 2 22 9 22 6 22 2 4 6 5 1 5 5 6 1 6 7 5 1 4 6 4 1 3 7 3 3 PH kW PA kW COP TWUC C TWUC C W W Mod TAMB C 35 40 45 50 55 60 35 40 45 50 55 60 35 40 45 50 55 60 15 11 5 11 9 12 4 13 0 4 4 4 9 5 4 6 1 2 6 2 4 2 3 2 1 10 13 4 13 7 14 0 14 5 15 0 4 6 5 0 5 6 6 2 7 1 2 9 2 7 2 5 2 3 2 1 7 14 7 14 9 15 2 15 5 15 9 16 4 4 7 5 1 5 7 6 3 7 1 8 1 3 1 2 9 2 7 2 5 2 2 2 0 5 15 6 15 8 16...

Страница 14: ...ity and its temperature can be calculated in the table at pages 12 13 14 depending on the ambient and the user water outlet conditions The table below shows the capacity of the model LZT13 SW6 PH kW PA kW COP TWUC C TWUC C W W Mod TAMB C 35 40 45 50 55 60 35 40 45 50 55 60 35 40 45 50 55 60 15 7 1 7 3 7 6 8 0 2 7 3 0 3 3 3 7 2 6 2 5 2 3 2 2 10 8 2 8 4 8 6 8 9 9 2 2 8 3 0 3 4 3 7 4 2 2 9 2 8 2 6 2 ...

Страница 15: ...12 13 14 15 The cooling capacity and the compressors input power in different working conditions can be obtained by multiplying the nominal values PF PA with their respective correction factors The diagram above indicates the correction factors for each curve the relative ambient conditions assuming that the difference between inlet and outlet cold water temperature is 5 C 30 C 40 C 35 C 25 C 20 C...

Страница 16: ...USER HEAT EXCHANGER WATER PRESSURE DROPS 20 30 40 50 800 1000 1200 1400 1600 1800 2000 20 30 40 50 2000 3000 4000 5000 B LZT 05 C LZT 07 D LZT 09 E LZT 13 G LZT 20 25 20 25 30 35 40 45 50 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 I LZT 30 M LZT40 E D C B G I M ...

Страница 17: ...C HOT WATER HEAT EXCHANGER WATER PRESSURE DROPS 20 30 40 50 800 1000 1200 1400 1600 1800 2000 20 30 40 50 2000 3000 4000 5000 B LZT 05 C LZT 07 D LZT 09 E LZT 13 G LZT 20 25 20 25 30 35 40 45 50 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 I LZT 30 M LZT40 I M E D C B G ...

Страница 18: ...AVAILABLE STATIC PRESSURE 20 30 40 50 60 70 80 600 800 1000 1200 1400 1600 1800 20 30 40 50 60 70 80 90 100 110 120 130 140 2000 2500 3000 3500 4000 4500 B LZT 05 C LZT 07 D LZT 09 E LZT 13 G LZT 20 25 20 40 60 80 100 120 140 160 180 4000 5000 6000 7000 8000 I LZT 30 M LZT 40 B E F I C D G M ...

Страница 19: ...05 07 09 higher values may call the action of safety devices with unit stop Cold water temperature summer operation The minimum temperature allowed at the evaporator outlet is 5 C To work below this limit the unit should need some structural modifications In this case contact our company The maximum temperature allowed at the evaporator outlet is 15 C Ambient air temperature The units are designed...

Страница 20: ... Cooling capacity correction factor IPCF Input power correction factor SOUND DATA LZT LS LOW NOISE VERSION Octave bands Hz Lw Lp 63 125 250 500 1K 2K 4K 8K Mod dB dB dB dB dB dB dB dB dB dB A dB A 05 07 80 9 72 3 66 2 64 7 63 6 58 2 54 8 45 7 81 9 68 0 40 0 09 09T 80 9 72 3 66 2 64 7 63 6 58 2 54 8 45 7 81 9 68 0 40 0 13 81 9 73 3 67 2 65 7 64 6 59 2 55 8 46 7 82 9 69 0 41 0 20 86 9 78 3 72 2 70 7...

Страница 21: ... disconnected INSPECTION When installing or servicing the unit it is necessary to strictly follow the rules reported on this manual to conform to all the specifications of the labels on the unit and to take any possible precautions of the case Not observing the rules reported on this manual can create dangerous situations After receiving the unit immediately check its integrity The unit left the f...

Страница 22: ...ase frame If it is the case it is possible to install anti vibration mounts spring or rubber to keep vibrations at a very low level Absolute care must be taken to ensure adequate air volume to the condenser Re circulation of discharge air must be avoided failure to observe this point will result in poor performance or activation of safety controls For these reasons it is necessary to observe the f...

Страница 23: ...3 MOD A B C D E 25 1000 800 800 800 3000 30 1000 800 800 800 3000 40 1000 800 800 800 3000 INSTALLATION OF THE HOODS The sound attenuation hoods are supplied loose they have to be mounted on the unit by Self screwing screws M3 5 x 16 supplied in the installation kit ...

Страница 24: ...and the hydraulic pressure drops of the system All pipes must be insulated with closed cell material of adequate thickness The chillers have to be connected to the piping by using flexible joints Piping should include Temperature and pressure gauges for the ordinary maintenance or servicing operations Shut off manual valves to separate the unit from the hydraulic circuit Metallic filters to be mou...

Страница 25: ...NTS A System filling group L Water pump B Thermometer M One way valve C Flexible connection N Evaporator D Ball shut off valve O Flow switch E Water strainer P User Water tank F Expansion vessel Q Water manometer G Safety valve R Domestic hot water accumulator H Vent valve S Domestic hot water feeding I Water tank Drainage valve ...

Страница 26: ...LZT High efficiency air to water heat pumps MTLZTGB REV 012008 26 DOMESTIC HOT WATER HYDRAULIC CONNECTIONS SW6 VERSIONS ONLY ...

Страница 27: ...er sensor MC Compressor BTO Supply water sensor SFW Flow switch CH Charging plug SHP High pressure switch CN Source heat exchanger SLP Low pressure switch CNSW Domestic hot water heat exchanger SV Manual valve ECO Economizer VR One way valve EV User heat exchanger VRV Reverse cycle valve EXV Thermostatic valve VSH High pressure safety valve FL Refrigerant filter YBP Hot gas by pass valve IV Sight ...

Страница 28: ...ed by the sensor is lower than the required set point VSH BTI BTO SFW VR M MFA LR FL SV EXV MFC M NO NC BPH MC SLP SHP CH VRV CH YBP IV ECO VR EXV YBP VR YW EV CNSW CN YL The LZT SW6 unit allows the production of cold and hot water independently from the operation mode of the unit heating or cooling During winter operation if domestic hot water is required it is temporarily stopped the water flow ...

Страница 29: ...he area near the cooling openings START UP Before start up Check that all power cables are properly connected and all terminals are hardly fixed The voltage at the phase R S T is the one shown in the unit labels Check that there is not any refrigerant leakage Check that crankcase heaters are powered correctly Check that all water connections are properly installed and all indications on unit label...

Страница 30: ...escribed in this chapter MUST BE DONE BY TRAINED PEOPLE ONLY Before every operation of servicing on the unit be sure that the electric supply is disconnected The top shell and discharge line of compressor are usually at high temperature level Be very careful when operating in their surroundings Aluminium coil fins are very sharp and can cause serious wounds Be very careful when operating in their ...

Страница 31: ... of its life and needs to be removed or replaced the following operations are recommended the unit refrigerant has to be recovered by trained people and sent to proper collecting centre compressor lubricating oil has to be recovered and sent to proper collecting centre the frame and various components if not usable any longer have to be dismantled and divided according to their nature particularly...

Страница 32: ...ance warning Running hour CO15 Manual Proceed with the hour reset procedure A15 Water pump maintenance Warning Running hour warning Manual Proceed with the hour reset procedure rtC Clock alarm Need to set the clock time Manual Set the clock and then proceed with manual reset rtF Clock alarm Faulty clock control Manual Proceed with manual reset if nothing happens change the clock EE EEPROM error al...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ... Tel 390 49 9731022 Fax 390 49 5806928 I In nf fo o h hi id dr ro os s i it t www hidros it Technical data shown in this booklet are not binding HIDROS SRL shall have the right to introduce at any time whatever modifications necessary to the improvement of the product ...

Отзывы: