© 1995-2009 Energy Saving Products Ltd.
The
WCM/WM
coil is a High Capacity Hydronic Water
Coil available as an add-on module to the Hi-Velocity
System. Mainly used in the chilled water applications for
cooling, this coil can also be used for heating with water
temperatures up to 130°F
(54°C)
.
When the potential for gravity flow of the hot water
exists, check valves may be needed on both the
supply and return lines. All lines should be piped so as
not to restrict access to the front panels, filter section,
or electrical enclosure. Size your supply and return
lines according to
Table 01
.
Piping the WCM/WM
The coil comes as a module and must be installed in the
vertical position on the return air side of the fan coil. The
WCM/WM come supplied with two L mounting brackets
for connection to the fan coil
(Fig. 01)
. When mounting
the cooling coil, ensure that no screws puncture the
drain pan or coil.
The WCM comes complete with 2 built-in 3/4”
(19mm)
drain lines, primary and secondary. Ensure the primary
drain line is vented and P-trapped.
The use of a mixture of gylcol will reduce capacities;
refer to gylcol manufacture reduction charts.
Chilled
Water Coil (WCM/WM)
Installation
Fig. 01 - Mounting the WCM/WM
Module WCM
Chilled Water Coil (WCM/WM) (1/1)
Module WCM Chilled Water Coil (WCM/WM) (1/1)
Table 1 - WCM/WM pipe sizing
Zone BTUH
Pipe Size
up to 40 feet
Pipe Size
40 – 100 feet
0 - 35,000
(0 - 10.3 kW)
3⁄4”
(19mm)
3⁄4”
(19mm)
35,001 - 70,000
(10.4 - 20.5 kW)
3⁄4”
(19mm)
1”
(25mm)
70,001 - 140,000
(20.6 - 41 kW)
1”
(25mm)
1
1⁄4
”
(32mm)
Specifications
WCM - 50
WCM - 70/1050 WM - 100/1050
WM - 1750
Matching Fan Coi
l
HE/HV-50/51/52
LV-50
HE/HV-70/71
LV-70
LV-E-1050
HE/HV-100/101
LV-120/140
LV-E-1050
LV-E-1750
Part Number
10010201050
10010201070
10010201100
20090101750
Fin Material
Aluminum
Aluminum
Aluminum
Aluminum
Tubing Material
Copper
Copper
Copper
Copper
Type of Fins
.006 Al
(0.1524mm)
.006 Al
(0.1524mm)
.006 Al
(0.1524mm)
.006 Al
(0.1524mm)
Flow Rate (GPM)
5
(0.32 L/s)
7
(0.44 L/s)
10
(0.63 L/s)
10
(0.63 L/s)
Hydronic
Connection
Sizes
Supply Line
3/4”
(19mm)
3/4”
(19mm)
3/4”
(19mm)
1
1⁄8
” (29mm)
Return Line
3/4”
(19mm)
3/4”
(19mm)
3/4”
(19mm)
1
1⁄8
” (29mm)
Drain Connection
3/4”
(19mm)
3/4”
(19mm)
3/4”
(19mm)
3/4”
(19mm)
Pressure Drop FT. H
2
O
3
(9.0 kPa)
6.5
(19.4 kPa)
6.8
(20.3 kPa)
4.9
(14.65 kPa)
Shipping Weight
30 lbs
(14 kg)
35 lbs
(16 kg)
40 lbs
(18 kg)
45 lbs
(20 kg)
Module Size (L x W x H)
14
3⁄8
” x 10
1⁄8
” x 18
1⁄2
”
(365mm x 257mm x 470mm)
19
3⁄8
” x 10
1⁄8
” x 18
1⁄8
”
(492mm x 257mm x 460mm)
25
3⁄8
” x 7” x 18
3⁄8
”
(645mm x 178mm x 467mm)
26
1⁄4
” x 8” x 22
5⁄8
”
(656mm x 203mm x 575mm)
BTUH
80°/67° @ 42°F E.W.T.
(27°/19 @ 5.5°C E.W.T.)
18,000-24,000
(5.3-7.0 kW)
30,000-36,000
(8.8-10.6 kW)
42,000-60,000
(12.3-17.6 kW)
42,000-70,000
(12.3-20.5 kW)