3.
Install the new fan assembly in the chassis:
a.
Orient the new fan assembly as shown in
, with the captive screw
on the right.
b.
Gently push the fan assembly into the chassis until it is firmly seated.
CAUTION:
Do not force the installation. If the fan assembly does not slide in easily,
ensure that it is correctly oriented before continuing.
c.
Secure the fan assembly to the chassis with the captive screw.
4.
Verify that the fan status LED is lit steady green to indicate normal operation (see
5.
(Optional) Display the fan status using the
fanshow
command from the CLI (see
for the locations of Fan assembly #1, Fan assembly #2, and Fan
assembly #3).
Figure 37 Inserting the fan assembly in the 8/80 SAN Switch
4. Status LED
1. 8/80 SAN Switch
5. Handle
2. Fan assembly unit
6. Nonport side
3. Captive screw
Replacing an 8/80 SAN Switch or Encryption SAN Switch power supply
CAUTION:
If a power supply fails, leave the power supply in the switch until it can be replaced.
Maintain both power supplies in operational condition to provide redundancy.
Replacing an 8/80 SAN Switch or Encryption SAN Switch power supply
69