12 Central dust monitoring (applies from software version 2.10)
Central dust monitoring" is available as an option. Here, up to 3 central dust sensors are
located in the clean gas duct, which monitor the dust level of all chambers.
The dust signal is monitored during the pause time in relation to the previously controlled
valve. The break time is the monitoring window.
Note!
The parameters for dust monitoring can be found in
chapter 9.2
The dust curve is shown over different time windows. The Y-axis of the monitoring graph is
dynamically scaled.
Figure 19
Trend chart dust course
The Y-axis of the monitoring chart is dynamically scaled.
1
Display dust history
20 seconds is the smallest possible step. Pulses and monitoring windows are also
visible.
2
Actual dust value
3
Chamber/ valve of the last pulse or the last monitoring window
4a
Pulse
4b
Monitoring window
The monitoring window begins with the valve pulse and ends with the end of the
subsequent pause.
5
Toggle between current data or pause.
6
Threshold Pre-alarm
Dust graph stopped due to main alarm
7
Threshold Main alarm
1
2
6
7
4b
3
5
4a