32
HE 5760 Operating Instructions
# 372449| Version 3.2
1.5 Valves 1. manifold
12
, 1…12
When using a pressure tank, this is the number of valves.
With two pressure tanks, half the valves.
If two pressure tanks are used per HE 5725 and the distribution is not even, this parameter
indicates the number of valves on the 1st pressure tank. Pressure tank. This information is
needed to select the correct pressure transmitter for valve monitoring. Without valve
monitoring function (10.6) the parameter has no meaning.
9.3.2 On site service
2.1 Language
0,
0…1
All display texts can be shown in two languages. The language elements are stored in a non-
volatile part of the memory. The control itself works language-independently with internal text
numbers. Each text number stands for a word or phrase. This parameter selects the current
language set. The complete text list for the 2. Language must be loaded in the control unit to
be selectable.
2.2 Synchronous time
-1
, -
1…1439
Always visible (Profibus or Modbus)
9.3.3 Interfaces
3.1 Interface PLC (control technology)
none
, Profibus, Modbus RTU
The interface used between control technology (PLC) and this control.
Two interfaces between control technology and master control are optionally available.
'PROFIBUS-DP' or 'Modbus-RTU' as fieldbus slave. This gives access to the complete
process image of the plant. Modbus RTU communication takes place via RS-485.
3.2 Device address Profibus or Modbus
12
, 1…255
3.3 dp source
A-In 1
, No, A-In 2, PLC
3.4 Sys-P source
A-In 2
, No, A-In 1, PLC
3.3 Modbus baud rate
3, 0
...5 kBaud
3.4 Modbus Parity
2
,
0…3