9.3.4 Valve control
4.1 Operation mode
Permanent,
Threshold
, Control, sets the start/stop condition of the cleaning process.
Requirement:
The wiring of the inputs 'Filter Start', 'Filter Stop' etc. have been done correctly.
'Permanent'
Start/stop are only dependent on the wiring of the inputs.
'Threshold'
Start/stop depending on input wiring and dp signal (threshold is defined with special
parameters)
'Regulation'
It is regulated to a dp value. Output size is the pause time. Additionally
a pause time extension can be made according to a characteristic curve with 10 coordinate
pairs (parameters 11.4 - 11.14)
4.2 Cleaning mode
PartCycle 0
, TotalCyc. 1
Setting whether to clean with complete cycles or with partial cycles.
4.3 Manual cleaning mode
Permanent
, Threshold, Regulation
Defines the start/stop condition of manual cleaning.
'Permanent'
Start/stop are only dependent on the wiring of the inputs.
'dp Threshold'
Start/stop depending on the input wiring and the dp
signal
(Threshold is defined with special parameters)
'Regulation'
It is regulated to a dp value
. Output size is the pause time.
In addition, a pause time extension can be set according to a characteristic
curve with 10
coordinate pairs can be made (parameters 14.4 - 14.14)
4.4 Valve sequence
1
, 1…23
Increment amount for calculating the next active valve within a chamber.
4.5 Chamber sequence
1
,
0…47
Increment amount for the calculation of the next active chamber.