Chapter 8 Error messages
30
Operating manual HE 5422 MR
Version 1.2
8
Error messages
Display
Cause
Remedy
The differential pres-
sure display shows
the following while
flashing:
EEPROM Parameter
Error
Restore factory settings
and check parametriza-
tion.
If this is not successful,
send the unit in for repair.
The differential pres-
sure display shows:
The differential pressure
signal is below the per-
missible measuring
range
Check differential pres-
sure.
Check external glands.
The differential pres-
sure display shows:
The differential pressure
signal is above the per-
missible measuring
range
Check differential pressure
signal.
Check external glands.
The differential pres-
sure display shows:
Error of the measuring
hose cleaning valve 1 (to
3);
Interruption
Send the device in for
repair.
The differential pres-
sure display shows:
Error of the measuring
hose cleaning valve 1 (to
3); Over-current
Send the device in for
repair.
Press ENTER for reset the
the error message
The high alarm LED
flashes.
The differential pressure
exceeds the configured
threshold
Adjust the configured
pulse and pause times.
Check the filter element.
Check the solenoid valves
for proper mechanical
functioning.
Check the compressed air
system.
The low alarm LED
flashes.
The differential pressure
falls below the configured
threshold for more than 5
minutes without reaching
the post cleaning thresh-
old
Adjust the configured
pulse and pause times.