background image

Chapter 2 Safety information

Operating manual  HE 5422 MR

9

Version 1.2

2.2

Safety during the individual phases of operation

The following safety notes must be observed when installing the device and during operation.

Danger of electric shock!

Disconnect the power supply before working on the device. Install the electrical 
lines in accordance with the respectively applicable local regulations (VDE 0100 
in Germany). Lay the measuring lines separately from the power lines. Produce a 
connection  between  the  protective  ground  connection  (in  the  respective  device 
carrier) and a protective ground.

Danger of electric shock!

Any interruption of the protective ground in the device carrier may cause the de-
vice to become dangerous. Deliberate interruptions are not permissible. If it can 
be  assumed  that  safe  operation  is  no  longer  possible,  then  the  device  shall  be 
put out of commission and be secured against unintended operation or re-activa-
tion.

Danger of electric shock!

Do  not  open  the  device  under  voltage!  When  opening  the  devices  or  removing 
covers  and  parts,  live parts  may  become exposed.  Connecting  points  may  also 
be live!

Caution!

The  device  may  not  be  put  into  operation  when  there  is  visible  damage  on  the 
device.

Caution!

Observe  the  accident  prevention  regulations  applicable  to  the  system,  such  as 
BGV A 3 "Electrical Systems and Equipment" during installation, commissioning, 
maintenance and troubleshooting.

Caution!

Clean soiled contacts using oil-free compressed air or spirit and a lint-free cloth.

Material damage due to electrostatic charging!

Observe the safety measures according to DIN EN 61340-51/-3 in order to pre-
vent electrostatic discharging!

Содержание HE 5422 MR

Страница 1: ...HE 5422 MR Differential pressure regulator with measuring hose cleaning Operating manual Translation of the operating manual Original version German...

Страница 2: ...lter Schr der Werner Brandis Publisher HESCH Industrie Elektronik GmbH Documentation Department Copyrights Copyright 2014 HESCH Industrie Elektronik GmbH All rights reserved The content including pict...

Страница 3: ...13 3 4 Technical data 14 4 Installation 16 5 Electrical commissioning 17 5 1 Safety notes 17 5 2 Supply voltage 18 5 3 Connection diagram 19 5 4 Inputs 19 5 5 Outputs 19 6 Parametrization 20 6 1 Param...

Страница 4: ...Chapter 3 Device description Description of the Differential Pressure Regulator control elements and techni cal specifications Chapter 4 Installation Dimensions of the device and scope of delivery Cha...

Страница 5: ...ter 3 1 3 4 5 2 5 3 Changed value for wide range power supply 100 240 VAV Chapter 2 2 Changed value for surface temperature Chap ter 6 1 Supplemented factory setting of p Measuring range mbar Chapter...

Страница 6: ...iable for improper usage and the resulting personnel injuries or damage the risk lies entirely with the operator Failure to comply with the above mentioned criteria regarding intended use may void the...

Страница 7: ...king with the de vice Used symbols The following symbols are used in this manual All safety information notes are structured in a uni form manner Warning of personnel injury The severity of the danger...

Страница 8: ...nger with medium risk that may result in death or serious injury if not avoided CAUTION Indicates a danger with low risk that might result in slight or moderate injury if not avoided Structure of warn...

Страница 9: ...berate interruptions are not permissible If it can be assumed that safe operation is no longer possible then the device shall be put out of commission and be secured against unintended operation or re...

Страница 10: ...zone 22 with the lid closed Prior to opening the device it has to be ensured that there are no explosive ambient conditions such as dust development The device is marked with II Not suitable for mine...

Страница 11: ...Chapter 3 Device description Operating manual HE 5422 MR 11 Version 1 2 3 Device description 3 1 Overview Fig 3 1 Overview A Type designation B Display and control elements C Cable glands A B C...

Страница 12: ...ration message Cleaning active Alarms active Interruption on one valve Short circuit of a valve over current Filter constant of the differential pressure measurement Post cleaning time Normal operatio...

Страница 13: ...essure balance after the blowing time Interval waiting time until the next measuring line cleaning cycle TEST button testing mode ON OFF PARA button parametrization mode ON OFF UP button increase disp...

Страница 14: ...mA Galvanically isolated Max permissible load 400 Digital inputs Start post cleaning Internally supplied by 24 VDC 1 mA Relay outputs 1 change over contact 250 VAC 5 A as a combined operating and fau...

Страница 15: ...mm hose Blowing pressure connection 1 push in bulkhead connector for 8 mm hose Maximum blowing pressure 8 bar Installation Wall mounting mounting position vertical Ambient conditions Climatic Storage...

Страница 16: ...ce may be installed in areas subject to the EX ATEX Zone 22 Explosion Class The special provisions should be observed see chapter 2 2 Safety dur ing the individual phases of operation on page 9 Dimens...

Страница 17: ...limitations specified for use of the device have to be observed before and during operation The protective ground connection in the appropriate device carrier has to be conductively connected to the p...

Страница 18: ...Supply voltage 1 Loosen the screws on the housing cover lid and remove the cover 2 Read the supply voltage value off the type plate for example 100 240 VAC and 24 VDC mains voltage 3 Connect PE conduc...

Страница 19: ...ed with 24 V DC and are active when they are switched to ground GND with a potential free contact 5 5 Outputs Relay The device is equipped with 4 potential free relay outputs The contacts can each be...

Страница 20: ...t value The next digit will subsequently flash in the display 6 Repeat steps 4 5 until the last digit has been changed The next parameter is offered 7 If necessary change the next parameter 8 The para...

Страница 21: ...len below of End of the p cycle OFF 0 1 450 mbar 10 0 mbar Low alarm mbar Threshold for the low alarm message When this value is fallen below of the relay contact is closed if the post cleaning thresh...

Страница 22: ...elow the low alarm threshold until the low alarm relay is activated The relay is not activated if the post cleaning threshold is fallen below of during this delay period 1 3600 s 300 s BG Cleaning int...

Страница 23: ...trization mode is exited If the current code is supposed to be read out the UP DOWN buttons again have to be pressed while powering up If 0 is selected as code the parameter protection is deactivated...

Страница 24: ...ns at the same time while powering up EEP will appear on the display 2 Hold both buttons for 5 seconds With a password 0 cod will flash in the display 3 Press the ENTER button 4 Change the code for th...

Страница 25: ...and the inputs of the device Fig 7 1 Connection compartment Note All digital inputs of a system refer to the same ground It is permissible to use one ground wire for multiple inputs A 1 As long as the...

Страница 26: ...1 The Upper threshold is exceeded or the Lower threshold is fallen below of 2 The Post cleaning threshold is fallen below of for the post cleaning time if the lower threshold was exceeded previously...

Страница 27: ...asuring range For example 0 30 mbar 4 20 mA 0 20 mbar 4 20 mA During normal operation the cleaning process is started when the upper threshold Cleaning is ex ceeded and is deactivated again when the l...

Страница 28: ...differential pressure measurement Cleaning Time Measuring range of the sensor High alarm Upper threshold Cleaning start Lower threshold Cleaning stop Low alarm Post cleaning start On Off High alarm r...

Страница 29: ...ential pressure measurement is regularly blocked off and compressed air is blown into the connection lines for raw and pure gas After a recovery time for pressure balanc ing the differential pressure...

Страница 30: ...ial pressure signal Check external glands The differential pres sure display shows Error of the measuring hose cleaning valve 1 to 3 Interruption Send the device in for repair The differential pres su...

Страница 31: ...Chapter 9 Declaration of conformity Operating manual HE 5422 MR 31 Version 1 2...

Страница 32: ...cleaned regularly in order to avoid increased dust build up on the device Disposal Recycle metals and plastics Electrical and electronic components should be collected separately and be disposed of ac...

Отзывы: