Name
P11
External must temperature (Code protection):
The boiler will operate with the external set temperature (fixedly) as long as the analogue set
temperature does not exceed the set up temperature (50-100°C)
P12
Analog must active (Code protection):
Activates the analogues set point setting (Yes/No)
P13
External must temperature - 4mA (Code protection)
Setting up lower limit of analogue set temperature at 4 mA (20-100°C).
P14
External must temperature - 20mA (Code protection)
Setting up lower limit of analogue set temperature at 20mA (20-100°C).
P15
External must temperature - Min.(Code protection)
Setting up minimum analogue set temperature (20-100°C)
P16
External must temperature - Max. (Code protection)
Setting up maximum analogue set temperature (20-100°C)
P17
Backflow-must (Code protection)
Displays the actual back flow must temperature (55-70°C)
P18
Mixer runtime (Code protection)
Setting of the mixer runtime at mixer valve: (30-300sec)
P19
min. Pause (Code protection)
Setting the required waiting time of the mixer until the next regulation (5-50sec)
P20
KP (Code protection)
P-Term of the back flow control (0,50-3,50)
P21
KD (Code protection)
D-Term of the back flow control (0,50-3,50)
P22
Pre-ventilation time
Setting the Pre-ventilation time (10-60sec)
P23
Ignition insert
Setting the ignition insertion time (5-60sec)
P24
Ignition combustion room
Setting the Ignition combustion room (150-250°C)
P25
max. Flue gas temperature (Code protection):
Displays the flue gas temperature (120-250°C)
By pressing the button:
"On/Off":
The equipment is switched on/off
„F1“:
(
T) changes to the „TIME-MODE“-menu
„F2“:
scroll up
„F3“:
scroll down
„F4“:
Value can be changed